Installation manual
[ VIII Test Run Mode ]
- 175 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P550YSJM-A
PURY-P300YJM-A PURY-P250YJM-A
Model name of BC controller CMB-P108V-GA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor
35°C/ -
[95°F/ -]
Indoor unit
No. of connected units
Unit
5
No. of units in operation 5
Model
-
100/100/100/125/125
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 55 [181]
Amount of refrigerant
kg
[lbs-oz]
33.8 [75]
Outdoor
unit
Electric current A 18.2
Voltage V 400
Compressor frequency Hz 74 65
LEV open-
ing
Indoor unit
Pulse
325/325/325/387/387
BC controller (LEV1/LEV3) 2000/230
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.04/ 0.82 3.04/ 0.82
[441/ 119] [441/ 119]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.87/ 2.87
[416/ 416]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
86 [187] 86 [187]
Heat exchanger outlet
(TH3)
40 [104] 40 [104]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 41 [106] 41 [106]
Indoor unit
LEV inlet 19 [66]
Heat exchanger liquid
pipe (TH2)
6[43]