Installation manual
[ VIII Test Run Mode ]
- 169 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P300YJM-A PURY-P350YJM-A
Model name of BC controller CMB-P104V-G1 CMB-P104V-G1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - 20°C/ -
[68°F/ -] [68°F/ -]
Outdoor
7°C/ 6°C 7°C/ 6°C
[45°F/ 43°F] [45°F/ 43°F]
Indoor unit
No. of connected units
Unit
33
No. of units in operation 3 3
Model
-
100/100/100 100/125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 35 [115] 35 [115]
Amount of refrigerant
kg
[lbs-oz]
18.1 [40] 20.9 [47]
Outdoor
unit
Electric current A 9.2 11.4
Voltage V 400 400
Compressor frequency Hz 81 101
LEV open-
ing
Indoor unit
Pulse
332/332/332 332/406/406
BC controller (LEV1/LEV3) 110/660 110/730
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.68/ 0.58 2.88/ 0.60
[389/ 84] [418/ 87]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.64/ 2.32 2.84/ 2.52
[383/ 336] [412/ 365]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
81 [178] 84 [183]
Heat exchanger inlet
(TH6)
0 [32] 1 [34]
Accumulator inlet (TH5) -3 [27] -4 [25]
Accumulator outlet -4 [25] -4 [25]
Compressor inlet -4 [25] -4 [25]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 39 [102] 39 [102]
Heat exchanger gas pipe
(TH3)
70 [158] 70 [158]