Installation manual

[ VIII Test Run Mode ]
- 167 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P400YJM-A PURY-P450YJM-A
Model name of BC controller CMB-P108V-GA1 CMB-P108V-GA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C 27°C/ 19°C
[81°F/ 66°F] [81°F/ 66°F]
Outdoor
35°C/ - 35°C/ -
[95°F/ -] [95°F/ -]
Indoor unit
No. of connected units
Unit
44
No. of units in operation 4 4
Model
-
100/100/100/100 100/100/125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 45 [148] 45 [148]
Amount of refrigerant
kg
[lbs-oz]
22.9 [51] 22.9 [51]
Outdoor
unit
Electric current A 14.2 15.2
Voltage V 400 400
Compressor frequency Hz 97 111
LEV open-
ing
Indoor unit
Pulse
325/325/325/325 325/325/387/387
BC controller (LEV1/LEV3) 2000/200 2000/210
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.16/ 0.89 3.15/ 0.85
[458/ 129] [457/ 123]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.75/ 2.75 2.70/ 2.70
[399/ 399] [392/ 392]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
91 [196] 90 [194]
Heat exchanger outlet
(TH3)
42 [108] 40 [104]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 17 [63] 17 [63]
Heat exchanger liquid
pipe (TH2)
4 [39] 4 [39]