Installation manual

[ VIII Test Run Mode ]
- 166 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P300YJM-A PURY-P350YJM-A
Model name of BC controller CMB-P104V-G1 CMB-P104V-G1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C 27°C/ 19°C
[81°F/ 66°F] [81°F/ 66°F]
Outdoor
35°C/ - 35°C/ -
[95°F/ -] [95°F/ -]
Indoor unit
No. of connected units
Unit
33
No. of units in operation 3 3
Model
-
100/100/100 100/125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 35 [115] 35 [115]
Amount of refrigerant
kg
[lbs-oz]
18.1 [40] 20.9 [47]
Outdoor
unit
Electric current A 9.1 11.9
Voltage V 400 400
Compressor frequency Hz 74 95
LEV open-
ing
Indoor unit
Pulse
325/325/325 325/387/387
BC controller (LEV1/LEV3) 2000/180 2000/190
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.12/ 0.86 3.03/ 0.79
[453/ 125] [439/ 115]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.93/ 2.93 2.72/ 2.72
[425/ 425] [395/ 395]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
86 [187] 92 [198]
Heat exchanger outlet
(TH3)
41 [106] 40 [104]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 42 [108] 42 [108]
Indoor unit
LEV inlet 19 [66] 19 [66]
Heat exchanger liquid
pipe (TH2)
6 [43] 6 [43]