Installation manual

[ VIII Test Run Mode ]
- 165 -
HWE10050 GB
[7] Standard Operation Data (Reference Data)
1. Single unit (Standard)
(1) Cooling only operation
Operation
Outdoor unit model
PURY-P200YJM-A PURY-P250YJM-A
Model name of BC controller CMB-P104V-G1 CMB-P104V-G1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C 27°C/ 19°C
[81°F/ 66°F] [81°F/ 66°F]
Outdoor
35°C/ - 35°C/ -
[95°F/ -] [95°F/ -]
Indoor unit
No. of connected units
Unit
22
No. of units in operation 2 2
Model
-
100/100 125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 25 [82] 25 [82]
Amount of refrigerant
kg
[lbs-oz]
16.3 [36] 17.5 [39]
Outdoor
unit
Electric current A 8.7 7.4
Voltage V 400 400
Compressor frequency Hz 52 65
LEV open-
ing
Indoor unit
Pulse
325/325 387/387
BC controller (LEV1/LEV3) 2000/160 2000/170
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.96/ 0.80 2.96/ 0.78
[429/ 116] [429/ 113]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.81/ 2.81 2.81/ 2.81
[408/ 408] [408/ 408]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
90 [194] 85 [185]
Heat exchanger outlet
(TH3)
39 [102] 39 [102]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 47 [117] 40 [104]
Indoor unit
LEV inlet 19 [66] 19 [66]
Heat exchanger liquid
pipe (TH2)
6 [43] 6 [43]