Installation manual

[ VI Refrigerant Circuit ]
- 79 -
HWE10040 GB
[2] Principal Parts and Functions
1. Outdoor unit
Part
name
Symbols
(functions)
Notes Usage Specifications Check method
Com-
pressor
MC1
(Comp1)
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
P200 - 250 and EP200 mod-
els
Low-pressure shell scroll
compressor
Wirewound resistance
20°C[68°F] : 0.71ohm
P300 - 450 models
EP250 · 350 models
Low-pressure shell scroll
compressor
Wirewound resistance
20°C[68°F] : 0.32ohm
High
pres-
sure
sensor
63HS1 1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
Low
pres-
sure
sensor
63LS 1) Detects low pressure
2) Provides low-pressure pro-
tection
Pres-
sure
switch
63H1 1) Detects high pressure
2) Provides high-pressure pro-
tection
4.15MPa[601psi] OFF setting
Electro-
magnet-
ic
contac-
tor
52F P450
and
EP300
only
Turns ON and OFF the output to
the fan motor.
AC220-240V Refer to the
section on
troubleshoot-
ing the outdoor
unit fan for the
ON/OFF pat-
tern of the
electromag-
netic
contactors.(pa
ge 277)
Pressure
0~4.15 MPa [601psi]
Vout 0.5~3.5V
0.071V/0.098 MPa [14psi]
Pressure [MPa]
=1.38 x Vout [V]-0.69
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63HS1
1
123
2
3
Pressure
0~1.7 MPa [247psi]
Vout 0.5~3.5V
0.173V/0.098 MPa [14psi]
Pressure [MPa]
=0.566 x Vout [V] - 0.283
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63LS
1
123
2
3