Installation manual

[ II Restrictions ]
- 18 -
HWE10040 GB
(2) High COP combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor units Composing units Maximum total ca-
pacity of connect-
able indoor units
Maximum num-
ber of connect-
able indoor units
Types of connectable
indoor units
EP200 YJM-A - - - 100 - 260 17 P15 - P200 models
R410A series indoor units
EP250 YJM-A - - - 125 - 325 21
EP300 YJM-A - - - 150 - 390 26
EP400 YSJM-A EP200 EP200 - 200 - 520 34 P15 - P500 models
R410A series indoor units
EP450 YSJM-A EP250 EP200 - 225 - 585 39
EP500 YSJM-A EP300 EP200 - 250 - 650 43
YSJM-A1 EP250 EP250 -
EP550 YSJM-A EP300 EP250 - 275 - 715 47
EP600 YSJM-A EP300 EP300 - 300 - 780 50
EP650 YSJM-A EP250 EP200 EP200 325 - 845
EP700 YSJM-A EP300 EP200 EP200 350 - 910
YSJM-A1 EP250 EP250 EP200
EP750 YSJM-A EP300 EP250 EP200 375 - 975
YSJM-A1 EP250 EP250 EP250
EP800 YSJM-A EP300 EP300 EP200 400 - 1040
YSJM-A1 EP300 EP250 EP250
EP850 YSJM-A EP300 EP300 EP250 425 - 1105
EP900 YSJM-A EP300 EP300 EP300 450 - 1170