[ II Restrictions ]
- 17 -
HWE10040 GB
II Restrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor units Composing units Maximum total ca-
pacity of connect-
able indoor units
Maximum num-
ber of connect-
able indoor units
Types of connectable
indoor units
P200 YJM-A - - - 100 - 260 17 P15 - P200 models
R410A series indoor units
P250 YJM-A - - - 125 - 325 21
P300 YJM-A - - - 150 - 390 26
P350 YJM-A - - - 175 - 455 30
P15 - P400 models
R410A series indoor units
P400 YJM-A - - - 200 - 520 34 P15 - P500 models
R410A series indoor units
P450 YJM-A - - - 225 - 585 39
P500 YSJM-A P250 P250 - 250 - 650 43
YSJM-A1 P300 P200 -
P550 YSJM-A P300 P250 - 275 - 715 47
P600 YSJM-A P350 P250 - 300 - 780 50
YSJM-A1 P300 P300 -
P650 YSJM-A P350 P300 - 325 - 845
P700 YSJM-A P350 P350 - 350 - 910
YSJM-A1 P400 P300 -
P750 YSJM-A P400 P350 - 375 - 975
P800 YSJM-A P450 P350 - 400 - 1040
YSJM-A1 P400 P400 -
P850 YSJM-A P450 P400 - 425 - 1105
P900 YSJM-A P450 P450 - 450 - 1170
P950 YSJM-A P400 P300 P250 475 - 1235
P1000 YSJM-A P400 P300 P300 500 - 1300
P1050 YSJM-A P400 P350 P300 525 - 1365
P1100 YSJM-A P400 P350 P350 550 - 1430
P1150 YSJM-A P450 P350 P350 575 - 1495
P1200 YSJM-A P450 P400 P350 600 - 1560
P1250 YSJM-A P450 P450 P350 625 - 1625