Installation manual

[ VIII Test Run Mode ]
- 139 -
HWE10040 GB
Operation
Outdoor unit model
PUHY-P900YSJM-A
PUHY-P450YJM-A PUHY-P450YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor 35°C/- [95°F/- ]
Indoor
unit
No. of connected
units
Unit
9
No. of units in opera-
tion
9
Model - 100/100/100/100/100/100/100/100/100
Piping
Main pipe
m [ ft ]
5[17]
Branch pipe 10 [33]
Total pipe length 95 [312]
Fan speed - Hi
Amount of refrigerant
kg
[ lbs-oz ]
39.8 [88]
Outdoor
unit
Electric current A 51.4
Voltage V 400
Compressor frequency Hz 111 111
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/325/325/325/325
SC (LEV1) 171 171
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
3.12/ 0.83 3.12/ 0.83
[453/ 120] [453/ 120]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
98 [208] 98 [208]
Heat exchanger out-
let (TH3)
47 [117] 47 [117]
Accumulator inlet 7 [45] 7 [45]
Accumulator outlet 7 [45] 7 [45]
SCC outlet (TH6) 26 [79] 26 [79]
Compressor inlet 20 [68] 20 [68]
Compressor shell
bottom
47 [117] 47 [117]
Indoor
unit
LEV inlet 26 [79]
Heat exchanger
outlet
4[39]