Installation manual
[ VIII Test Run Mode ]
- 128 -
HWE10040 GB
Operation
Outdoor unit model
PUHY-P500YSJM-A1
PUHY-P200YJM-A PUHY-P300YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor 35°C/- [95°F/- ]
Indoor
unit
No. of connected
units
Unit
5
No. of units in opera-
tion
5
Model - 100/100/100/100/100
Piping
Main pipe
m [ ft ]
5[17]
Branch pipe 10 [33]
Total pipe length 55 [181]
Fan speed - Hi
Amount of refrigerant
kg
[ lbs-oz ]
23.6 [52]
Outdoor
unit
Electric current A 24.1
Voltage V 400
Compressor frequency Hz 52 74
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325
SC (LEV1) 80 105
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
2.77/ 0.74 2.86/ 0.69
[402/ 107] [415/ 100]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
89 [192] 90 [194]
Heat exchanger out-
let (TH3)
44 [111] 43 [109]
Accumulator inlet 7 [45] 7 [45]
Accumulator outlet 7 [45] 7 [45]
SCC outlet (TH6) 22 [72] 24 [75]
Compressor inlet 19 [66] 19 [66]
Compressor shell
bottom
47 [117] 48 [118]
Indoor
unit
LEV inlet 24 [75]
Heat exchanger
outlet
6[43]