Installation manual

[ VIII Test Run Mode ]
- 122 -
HWE10040 GB
Operation
Outdoor unit model
PUHY-P300YJM-A PUHY-P350YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C 27°C/ 19°C
[81°F/ 66°F] [81°F/ 66°F]
Outdoor 35°C/- [95°F/- ] 35°C/- [95°F/- ]
Indoor
unit
No. of connected
units
Unit
34
No. of units in opera-
tion
34
Model - 100/100/100 100/100/100/50
Piping
Main pipe
m [ ft ]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 35 [115] 45 [148]
Fan speed - Hi Hi
Amount of refrigerant
kg
[ lbs-oz ]
14.0 [31] 17.6 [39]
Outdoor
unit
Electric current A 14.4 17.6
Voltage V 400 400
Compressor frequency Hz 74 95
LEV open-
ing
Indoor unit
Pulse
325/325/325 325/325/325/362
SC (LEV1) 100 100
LEV2 - -
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
2.95/ 0.84 2.86/ 0.76
[428/ 122] [415/ 110]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
84 [183] 90 [194]
Heat exchanger out-
let (TH3)
44 [111] 43 [109]
Accumulator inlet 7 [45] 7 [45]
Accumulator outlet 7 [45] 7 [45]
SCC outlet (TH6) 22 [72] 22 [72]
Compressor inlet 19 [66] 19 [66]
Compressor shell
bottom
42 [108] 42 [108]
Indoor
unit
LEV inlet 22 [72] 22 [72]
Heat exchanger
outlet
6 [43] 6 [43]