Specifications

Bringing a year round comfort solutions to
extreme climates
CITY MULTI ZUBADAN series combines the ultimate in application flexibility and powerful cooling and heating
capabilities to deliver precise comfort even in the coldest days of the year down to -25
˚C.
The technology behind this is a Flash Injection circuit which provides optimum amount of refrigerant to the system
via a compressor through a specially designed injection port to ensure a particularly stable operation. With this,
ZUBADAN can provide a full heating performance even at -15
˚C and continuous heating for up to 250 minutes in
one continuous cycle, ensuring a phenomenal heating performance at low temperatures.
ZUBADAN
Cooling or Heating
Installation image
System Pipe Lengths
*1 When the outdoor unit is installed below the indoor unit, top-bottom differential is 40m [131 ft].
Refrigerant Piping Lengths
Total length
Maximum allowable length
Farthest indoor from first branch
Vertical differentials between units
Indoor/outdoor (outdoor higher)
Indoor/outdoor (outdoor lower)
Indoor/indoor
Maximum meters [Feet]
300 [984]
150 (175equivalent)
[492 (574)]
40 [131]
Maximum meters [Feet]
50 [164]
40 [131]
15 [49]
[8-10HP]
PUHY-HP YHM-A(-BS)
PUHY-HP YSHM-A(-BS)
ZUBADAN series
Outdoor unit
Indoor unit
Between indoor units
top-bottom differential
15m [49ft]
Between indoor units
top-bottom differential
15m [49ft]
Top-bottom differential
50m [164ft]
Top-bottom differential
50m [164ft] *1
Furthest piping length
190m [623ft] (equivalent length)
(actual length 165m [541ft])
Furthest piping length
175m [574ft] (equivalent length)
(actual length 150m [492ft])
Header
Joint
Outdoor unit
15.5˚C
15.5˚C
Conventional CITY MULTI
PUHY-P TGMU
Hyper Heating Inverter System
Page87
Outdoor unit
ZUBADAN
Between indoor units
top-bottom differential
15m [49ft]
Top-bottom differential
50m [164ft]
Furthest piping length
190m [623ft] (equivalent length)
(actual length 165m [541ft])
Stable Heating Performance even at -15˚C
Expanded Heating Operation down to -25˚C
Using an industry first ‘Flash-injection
Circuit’, the ZUBADAN System is able
to provide FULL heating performance in
ambient temperatures as low as -15˚C.
…furthermore, from a previous LOWEST
operating ambient temperature of -20˚C,
the ZUBADAN System pushes the
boundaries of technology to give heating
in ambient temperatures as low as -25˚C.
Full heating
capacity even
at -15˚C
Capacity
improvement by
about 40%
Outdoor temp.˚C (W.B.)
PUHY-HP250 YHM-A
Standard CITY MULTI
PUHY-P400 YSHM-A
Standard CITY MULTI
PUHY-P250 YHM-A
PUHY-HP400 YSHM-A
45
28
(kW)
0
-25 -20
-15
-10 -5 0
3
Outdoor temp.˚C (W.B.)
-20-25 -10 0 10 20
-20˚C
Outdoor temperature
-25˚C
15.5˚C
15.5˚C
15.5˚C
15.5˚C
Expanded to -25˚C
Conventional CITY MULTI
PUHY-P PUHY-P TGMU
Hyper Heating Inverter System
Conventional CITY MULTI
PUHY-P YHM
ZUBADAN System
Outdoor temperature
-25˚C
With ZUBADAN System
Previously, heating performance
drops off when the temperature falls
below -20˚C!
…however, even at such temperatures,
the new ZUBADAN System has no
trouble keeping the occupants nice
and toasty!