Specifications

Specifications
Note:
1. The cooling and heating capacites are the maximum capacites that were obitained by operating in the above air conditions and with a refrigerant pipe of about 7.5m.
2 .The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical infomation.
3 .The operating noise is the data that was obitained by measuring it 1.5m from the the bottom of the unit in an anechoic room. (Noise meter A-scale value)
4 .The figure of Electrical characteristic indicates at 240V 50Hz/230V60Hz (PEFY-P80, 140VHM-E-F type), at 220Pa setting at 415V (PEFY-P200, 250VMH-E-F type).
5 . When the 100% fresh air indoor units are connected, the maximum connectable indoor units to 1 outdoor unit are as follows
Power source
Cooling capacity
Heating capacity
Power
consumption
Current
External finish
Dimension
H W D
Net weight
Heat exchanger
Fan
Motor
Air filter (option)
Refrigerant
pipe diameter
Field drain pipe diameter
Sound pressure level
(Lo-Mid-Hi) 2
Gas
(Flare)
Liquid
(Flare)
208, 220V
230, 240V
208V
220V
230V
240V
Type
Quautity
Airflow rate
External
static
pressure
(Lo-Mid-Hi)
Type
Output
Cooling
Heating
Cooling
Heating
kW
BTU/h
kW
BTU/h
kW
kW
A
A
mm(in.)
kg(lbs.)
m
3
/min
L/s
cfm
Pa
Pa
Pa
Pa
kW
mm(in.)
mm(in.)
mm(in.)
dB(A)
dB(A)
1
1
1
1
PEFY-P80VMH-E-F PEFY-P140VMH-E-F
9.0
30,700
8.5
29,000
0.16 / 0.21
0.16 / 0.21
0.67 / 0.91
0.67 / 0.91
380 1000 900
(15 39-3/8 35-7/16)
50 (111)
Sirocco fan 1
9.0
150
18
35 - 85 - 170
40 - 115 - 190
50 - 130 - 210
80 - 170 - 220
0.09 (at 220V)
27 - 38 - 43
33 - 43 - 45
16.0
54,600
15.1
51,500
0.29 / 0.33
0.29 / 0.33
1.24 / 1.48
1.24 / 1.48
380 1200 900
(15 47-1/4 35-7/16)
70 (155)
Sirocco fan 2
18.0
300
636
35 - 85 - 170
50 - 115 - 190
60 - 130 - 220
100 - 170 - 240
0.14 (at 220V)
28 - 38 - 43
34 - 43 - 45
1-phase 220-240V 50Hz / 1-phase 208-230V 60Hz
Galvanized
Cross fin (Aluminum plate fin and copper tube)
1-phase induction motor
Synthetic fiber unwoven cloth filter (long life)
ø15.88 (ø5/8)
ø9.52 (ø3/8)
O.D.32 (1-1/4)
Power source
Cooling capacity
Heating capacity
Power
consumption
Current
External finish
Dimension
H W D
Net weight
Heat exchanger
Fan
Motor
Air filter (option)
Refrigerant
pipe diameter
Field drain pipe diameter
Sound pressure
level 2
Gas
(Flare)
Liquid
(Flare)
380V
400V
415V
380V
400V
415V
Type
Quautity
Airflow rate
External
static
pressure
Type
Output
Cooling
Heating
Cooling
Heating
kW
BTU/h
kW
BTU/h
kW
kW
A
A
mm(in.)
kg(lbs.)
m
3
/min
L/s
cfm
Pa
Pa
Pa
kW
mm(in.)
mm(in.)
mm(in.)
dB(A)
dB(A)
dB(A)
PEFY-P200VMH-E-F PEFY-P250 VMH-E-F
22.4
76,400
21.2
72,300
0.34 / 0.42
0.34 / 0.42
0.58 / 0.74
0.58 / 0.74
28
467
989
140 / 200
150 / 210
160 / 220
0.20
ø19.05 (ø3/4)
39 / 42
40 / 43
40 / 44
28.0
95,500
26.5
90,400
0.39 / 0.50
0.39 / 0.50
0.68 / 0.86
0.68 / 0.86
35
583
1236
110 / 190
120 / 200
130 / 210
0.23
ø22.2 (ø7/8)
40 / 44
40 / 45
41 / 46
3N~ 380-415V 50Hz / 3N~ 380-415V 60Hz
Galvanized
470 1250 1120
(18-9/16 49-1/4 44-1/8)
100 (221)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan 2
3-phase induction motor
Synthetic fiber unmoven cloth filter (long life type)
ø9.52 (ø3/8)
O.D.32 (1-1/4)
6. Operational temp range is
Cooling : from 21˚C(70˚F)DB/15.5˚C(60˚F)WB to 43˚C(109˚F)DB/35˚C(95˚F)WB
Heating : from -10˚C(14˚F)DB to 20˚C(68˚F)DB
Thermo off(Fan) operation automatically starts either when temperature is lower than 21˚C(70˚F)DB in cooling mode or when the temperature exceeds 20˚C(68˚F)DB in heating mode.
7. As the room temp in sensed by the thermo in the remote controller or the one in the room, be sure to use either remote controller or room thermo.
8. Autochangeover function or Dry mode is NOT available. Fan mode operation during the thermo off in Cooling/Heating mode.
9. In any case, the air flow rate should be kept lower than 110% of the above chart. Please see "Fan curves" for the details.
10. When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
11. Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation.
Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also insulate rooms for dew condensation prevention as required.
12. Air filter must be installed in the air intake side. The filter should be attached where easy maintenance in possible in case of usage of fild supply filters.
13. Long life cannot be used with Hi-efficiency filter together (PEFY-P80
.
140VMH-E-F type).
Heat pump models
110%(100% in case of heating below-5˚C(23˚F))
Cooling only
110%
()
Specifications
Page56
Specifications
Fresh Air can be taken in with temperature control.
Ideal for Offices, Stores and Restaurants.
The Fresh Air intake indoor unit
can be installed in any place.
The Fresh Air intake indoor unit can take
fresh outdoor air into any building in any
place at any time.
* Limits of capacity connectable to outdoor unit
Max. 110% of outdoor unit capacity, excepting heating at outdoor temperature of less than -5˚C(23˚F) (100%).
Office, Lobby, Workshop,
Rest room, Nursing home,
Smoking corner,
Kitchen in restaurant
Fresh Air intake indoor unit
Fresh
air
OA
Supply air
Exhaust
air
EA
Installing fresh Air intake indoor unit (Image)
Example
2. Workshop1. Nursery home
Fresh Air intake
indoor unit
Fresh Air intake
indoor unit
Workshop
Office
Private room
Passage
Air flow
Ventilating fan
Private room
Fresh air
Polluted air
Exhaust
air
Ventilating fan
INDOOR UNIT
Fresh Air Intake Type
PEFY-P VMH-E-F
< Note>
Fan remains in operation during Thermo-OFF. Using this model with other type of indoor
unit is recommended to prevent cold draft which is caused due to intaken fresh air.
Fresh
Air Intake
Page55
Indoor unit