Specifications

Page38
Remote Controller
BACnet
®
and M-NET adapter (BAC-HD150)
Example of Basic System Configuration.
Central
monitor
BMS
BACnet/IP
BAC-HD150
BAC-HD150
BACnet/IP
CITY MULTI can easily combine into a Building Management System (BMS) via the BACnet
®
and M-NET adapter BAC-HD150. BACnet
is an opened transmission protocol widely used at BMS, and related equipment control. CITY MULTI is therefore compatible with large-
scaled BMS management via BACnet.
One BAC-HD150 manages up to 50 indoor units without software installation to PC.
M-NET
ME remote
controller
ME remote
controller
M-NET
ME remote
controller
PZ-52SF
LOSSNAY unit
FUNCTION
CONTENT
ON/OFF
Mode
Fan Speed
Airflow Direction
Set Temperature
Filter Sign reset
Permit/ Prohibit
Forced OFF
ON/OFF
Mode
Fan Speed
Air direction
Set Temperature
Filter sign
Permit/ Prohibit
Indoor temperature
Alarm signal
Error code
Communication state
BACnet
®
and M-NET adapter
Operation
Monitoring
Run/ Stop
Cool/ Dry/ Heat/ Auto/ Fan
Low-Mid1-Mid2-Hi
Horizontal- 60˚-80˚-100˚swing
Cooling 19-30˚C [67-87˚F], Heating 17-28˚C [63-83˚F], Auto 19-28˚C [67-83˚F]
Normal/ Reset
ON/OFF, Mode, Filter sign reset, Set temp.
Release/ Effective
Run/ Stop
Cool/ Dry/ Heat/ Auto/ Fan
Low-Mid1-Mid2-Hi
Horizontal- 60˚-80˚-100˚swing
Cooling 19-30˚C [67-87˚F], Heating 17-28˚C [63-83˚F], Auto 19-28˚C [67-83˚F]
Normal/ Reset
ON/OFF, Mode, Filter sign reset, Set temp.
-
Normal/ Abnormal
2 Character code- Indicates all unit alarms
Normal/ Abnormal
NO
software
installation
to PC.
Page37
Remote Controller