Diamondback BV-FF Ball Valve Installation Instructions

DO NOT DISASSEMBLE VALVE FOR ANY REASON. CONTACT FACTORY FOR DISPOSITION
Rotate flats on swivel type seal cap using adjustable wrench. Turn 90 degrees against the mechanical
stops. Align OPEN arrow with refrigerant line for non-directional flow. Turn clockwise to close.
Seal cap nut uses a 1-1/8” wrench Stem Cap located under Seal Cap Nut uses 3/8” wrench
o Note: Seal Cap Nut is factory set for proper torque value for correct operation and should not need
adjustment when installed
This valve contains mechanical stops DO NOT USE EXCESSIVE FORCE AGAINST STOPS OR
PERMANENT DAMAGE MAY OCCUR.
Follow the equipment manufacturer’s instructions when connecting valves to system and refrigerant
piping, and when evacuating system and testing for leaks.
Remove protective shipping plugs before connecting to equipment.
Properly tighten the flare connections and be careful not to over tighten. Use a torque wrench and
tighten to approved level. Make sure Schrader Cap is tight.
Apply a small amount of refrigerant oil to the flare face during installation for a proper and long lasting
seal. This will help ensure protection against leaks.
Install the insulator carefully, seal using adhesive flap provided. Tie bands may be used for additional
security.
Never allow contaminants to be introduced into the valve or piping.
“One Year Warranty” against defects in materials and workmanship from date of purchase.
For use with CFC, HCFC, and HFC Refrigerants listed in CAN/CSA B52 and ANSI/ASHRAE 15, Sect. 9.2 where
the saturation vapor pressure at 125º F (High Side) and 80º F (Low Side) is less than the maximum design
working pressure. After charging, mark unit with Refrigerant Type and Oil Type.
1340 Satellite Boulevard - Suwanee, GA 30024, USA
Phone: 678-376-2900FAX: 1-800-658-1458 email:
info@hvac,mea.com
2013 Mitsubishi Electric / HVAC
CA 07152013
Flare Size
Tightening Torque
Wrench Size
N-m
Ft. Lbs.
1/4”
14 18
10 13
5/8”
3/8”
34 42
25 30
13/16”
1/2"
49 61
35 44
15/16”
5/8”
68 - 82
49 59
1-1/16”
Diamondback™
BV-FF Series Unibody
Ball Valves