NEMA Enclosure Types

NEMA Enclosure Types
Table B-1
[From NEMA 250-2003]
Comparison of Specific Applications of Enclosures
for Indoor Hazardous Locations
(If the installation is outdoors and/or additional protection is required by
Table 1 and Table 2, a combination-type enclosure is required.)
Provides a Degree of Protection Against
Atmospheres Typically Containing
Enclosure Types 7 and
8, Class I Groups **
Enclosure Type 9,
Class II Groups
(See NFPA 497M for Complete Listing)
Class A B C D E F G 10
Acetylene I X ... ... ... ... ... ... ...
Hydrogen, manufactured gas I ... X ... ... ... ... ... ...
Diethyl ether, ethylene, cyclopropane I ... ... X ... ... ... ... ...
Gasoline, hexane, butane, naphtha, propane,
acetone, toluene, isoprene
I ... ... ... X ... ... ... ...
Metal dust II ... ... ... ... X ... ... ...
Carbon black, coal dust, coke dust II ... ... ... ... ... X ... ...
Flour, starch, grain dust II ... ... ... ... ... ... X ...
Fibers, flyings * III ... ... ... ... ... ... X ...
Methane with or without coal dust MSHA ... ... ... ... ... ... ... X
* For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500.
** Due to the characteristics of the gas, vapor, or dust, a product suitable for one Class or Group may not be suitable
for another Class or Group unless marked on the product.