NEMA Enclosure Types
NEMA Enclosure Types
Type 4X Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(windblown dust); to provide a degree of protection with respect to harmful effects on
the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose
directed water); that provides an additional level of protection against corrosion; and
that will be undamaged by the external formation of ice on the enclosure.
Type 5 Enclosures constructed for indoor use to provide a degree of protection to
personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects (falling dirt and
settling airborne dust, lint, fibers, and flyings); and to provide a degree of protection with
respect to harmful effects on the equipment due to the ingress of water (dripping and
light splashing).
Type 6 Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (hose directed water and the entry of water
during occasional temporary submersion at a limited depth); and that will be
undamaged by the external formation of ice on the enclosure.
Type 6P Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (hose directed water and the entry of water
during prolonged submersion at a limited depth); that provides an additional level of
protection against corrosion and that will be undamaged by the external formation of ice
on the enclosure.
Type 12 Enclosures constructed (without knockouts) for indoor use to provide a
degree of protection to personnel against access to hazardous parts; to provide a
degree of protection of the equipment inside the enclosure against ingress of solid
foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a
degree of protection with respect to harmful effects on the equipment due to the ingress
of water (dripping and light splashing).
Type 12K Enclosures constructed (with knockouts) for indoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of
protection with respect to harmful effects on the equipment due to the ingress of water
(dripping and light splashing).
National Electrical Manufacturers Association Approved by NEMA Enclosures Section
1300 N. 17
th
Street, Suite 1752 November 2005
Rosslyn, VA 22209