Specifications
CONTROLLER (Feb. 2009)
CNTR-75
CONTROLLER
DATA U4
4. SYSTEM COMPONENT
In a multi air conditionersystem that is a freeplan direct-expansion type,a connector for inputtingandoutputtingsignals
to/fromthe outsideis fittedas standardon the control boardofthe indoorandoutdoorunits.Use this when you want
each unit to input/outputsignalsindividually.(Note: When there are many control units it is recommendedthat you use
MELANS. This wouldenable you to save on labor.) In orderto have an input output signalfromeach connector,you must
have adedicatedadapter(sold separately) and a relay circuit (on-site arrangements).
Note :See next pagefor actual examples ofuse.
Category
Application
Input
Methodofdisablingcoolandheatoperation(thermo
off)byinputfromtheoutsidetotheoutdoorunit.
Output
Methodofreceivingasignalfromtheoutdoorunit
(water-sourceunit)totheoutside.
Canbeusedasadevicethatdisplays the oper-
ation state.
Canbeusedasaninterlockedcontrolwithex-
ternalequipment.
Typesofcontrolthatusesconnectorsfortheoutdoorunit/water-sourceunitinputoutputsignal
(connectionforeachtypeofoption).
Typesofcontrolthatusesconnectorsfortheindoorunitinputoutputsignal(connectionforeachtypeofoption)
Function
Connector
CategoryApplication Function
Connector
Input
(Note2,3)
MethodofON/OFFcontrolby turningonandoff switches or con-
tactsfromanoutsidetoeachindoorunitgroup.
Canbeusedasatimeradapter(Note1)
Canbeusedasa"forgettoswitchoffprevention"or"forcedstop".
Distant/local
switching(note1)
ON/OFF(level)
CN32
MethodofON/OFFcontrolby invertingstart/stopusingexternal
pulse(a-contact)foreachindoorunitgroup.
ON/OFF(pulse) CN51
Output
Methodofsendingsignalstooutsideforeachindoorunitgroup.
Itcanbeusedasadevicetodisplay operation states.
Itcanbeusedasaninterlockedcontrolwiththeexternalequip-
ment.
Operation state
Error state
Error state or
frostprevention
output (note 8)
Operation ON
signal(note9)
Operationmode
(heat) state
Operationmode
(cool,dry) state
Thermo ON
(fan) state
CN52
CN51
CompON/OFF
You can switchtheoperationmodebetweencooling
andheatingbyinputfromtheoutsidetotheoutdoor
unit.
Autochangeover
The lo
Forces the heat source unit to stop operation by
receivingcontactsignalsfromthepumpinterlock
circuit
wnoiseoperationoftheindoorunitcanbe
commencedby the externalinputtotheoutdoor
unit (water-source unit).
(Thenightmodecanbeadaptedonlyunder
f orheating)
Nightmode
PumpInterlock
signalinput
(level)
Compressor is
run state
CN3D
CN51
CN3D
CN3D
CN3D
CN51
TB8
TB8
TB8
TB8
Y, WYR2,WR2
less
CN3N
(W-Series) (W-Series)
Forcesoutdoorunittoperformafanoperationby
receivingsignalsfromthesnowsensor. (note 10)
Snow sensor
signalinput
CN3S
(Y-Series)
CN3S
(R2-Series)