Specifications

CONTROLLER (Feb. 2009)
CNTR-71
CONTROLLER
DATA U4
3-17-1. Specifications
3-17-1-1. Device Specifications
* This figure omits the power supply line and only shows the transmission line.
*1: The AI controller can be connected to G(B)-50A with Ver.3.20 or later.
*2: The AI controller can be connected to TG-2000A with Ver.5.10 or later.
<Restrictions>
Maximum of 50
units
per AG-150A/
G(B)-50A, 24 units per GB-24A.
However, the number of units that can be con
nected
to
an
AG-150A/G(B)-50
A
is
up
to
50 (to 24 with the GB-24A) including this device,
an indoor unit, LOSSNAY unit, etc.
NOTE
• For the shield ground of the M-NET centralized control line, use single-point grounding at the power unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor
unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit.
Furthermore, when connecting the M-NET transmission line of this device to the M-NET indoor control line,
use grounding at the TB3 for each outdoor unit system.
• If the M-NET transmission line of this device is connected to an M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the AI
controller cannot be set and monitored from the system controller.
The sensor connected to the AI controller can only be monitored from AG-150A, AG-150/G(B)-50A
Web
browser
/GB-24A
The sensor cannot be monitored from the G-50A LCD.
(1) Channel 1 temperature or humidity sensor input
(2) Channel 2 temperature or humidity sensor input
(3) Channel 1 upper/lower limit alarm output
(
4
)
Channel 2u
pp
er/lower limit alarm out
p
ut
M-NET
TB7
TB3
M-NET
LAN
(2)
(3) (4)
(1)
(2)
(3) (4)
(1)
LAN
Centralized control line
Indoor control line
AI controller
or G(B)-50A
*1
Power supply unit
PAC-SC51KUA
AG-150A/
G(B)-50
A Web
or TG-2000A
*2
CITY MULTI
Te mperature sensor,
humidity sensor,
etc.
AI controller
24 VDC Power
Supply
24 VDC Power
Supply
Upper/lower limit
alarm interlock
devices, etc.
Te mperature sensor,
humidity sensor,
etc.
Upper/lower limit
alarm interlock
devices, etc.
and TG-2000A.
AG-150A or
CENTRALIZED CONTROLLER AG-150A
3. SYSTEM CONTROLLER