Specifications
CNTR-62
CONTROLLER (Feb. 2009)
CONTROLLER
DATA U4
3-15. LonWorks
®
interface [LMAP03U]
LMAP
LMAP
Building management system
Protocol : L
ONWORKS
®
Lighting
Elevator
System example
CITY MULTI
®
can easily combine into a Building Management System (BMS) via the LONWORKS
®
and M-NET adapter
LMAP03U. L
ONWORKS
®
is an opened transmission protocol widely used at BMS and related equipment control.
CITY MULTI
®
is therefore compatible with large-scaled BMS management via LONWORKS
®
.
One LMAP03U serv
es up to 50 indoor units
. (CITY MULTI
®
, Mr. Slim
®
, and LOSSNAY
®
.)
On/Off
Mode
Set point from network (Set temp.)
Fan speed
Prohibit local On/Off
Prohibit local Mode
Prohibit local Set temp.
Batch Off
On/Off
Mode
Set point from network (Set temp.)
Fan speed
Thermo On/Off
Indoor temperature
Alarm signal
Prohibit local On/Off
Prohibit local Mode
Prohibit local Set temp.
Operation
State
Monitoring
Communication items at
L
ON
W
ORKS
®
and M-NET Adapter LMAP03U
3. SYSTEM CONTROLLER
3-15. LonWorks
®
interface [LMAP03U]