Specifications

CONTROLLER (Feb. 2009)
CNTR-43
CONTROLLER
DATA U4
3. SYSTEM CONTROLLER
4). Recommended circuit example
CN 2 Lead wire Details of each terminal
No.1 Green Common (External ground)
No.2 Black ON/OFF
No.3 Brown Malfunction/normal
(2). External signal output function
1). External output
When one or more air conditioners are running, the “ON” signal will be output and if a malfunction occurs in one or more air
conditioners, the “Malfunction” signal will be shown.
2). External output specifications
3). Recommended circuit example
Each element will turn on while ON operation or a malfunction occurs.
The connection cable can be extended up to 10m (32ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.
Use Z1 and Z2 relays having the following specifications.
Operation coil
Rated voltage :12VDC,24VDC
Power Consumption : 0.9W or less
( 1)Prepare a power supply separately according to the
relay being used. (12VDC or 24VDC)
( 2)Always insert a diode on both ends of the relay coil.
" ON" signal and " Malfunction" signal will
both be output.
External signal output requires the external I/o adapter (Model: PAC-YG10HA) sold separately.
The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm
2
(AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.
(A) For level signal
Red
Orange
Max.10m
(32 ft)
CN2
X1
Run/stop or
Emergency stop
Power supply
(12VDC or 24VDC)
This unit
9
8
7
6
5
X1
Max.10m
(32 ft)
This unit
CN2
Power supply
(12VDC or 24VDC)
Red
Gray
Blue
Ye llow
Orange
Y2
Y1
X2
X1
Run Stop Prohibit Enable
1
(B) For pulse signal
9
8
7
6
5
1
X1 X2 Y1 Y2
Brown
Black
Diode(*2)
Power
(*1)
Supply
Z1
Z2
CN2
Green
Max.10m
(32 ft)
L1: Run display lamp
L2: Malfunction display lamp
This unit
L1
L2
Z1
Z2
9
4
3
2
1
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
Rated voltage
Rated current
>= 12VDC
>= 0.1A
Minimum applicable load =< 1mA at DC
(*2)
(*2)