Specifications

CONTROLLER (Feb. 2009)
CNTR-31
CONTROLLER
DATA U4
Operation mode
switching
Te mperature
setting
Fan speed setting
Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.
Air flow direction
setting
Permit / Prohibit
local operation
Schedule
operation
This operates air conditioner units in test run mode.
Indoor unit intake
temperature
Measures the intake temperature of the indoor unit only when
the indoor unit is operating.
Error
Te st run
ON/OFF
Run and stop operation for the air conditioner units
Ventilation
equipment
External
input/output
Item
Description
Operations Display
Air flow direction angles, 4-angle or 5-angle Swing, Auto
1: Louver cannot be set.
Air flow direction settings vary depending on the model.
:Each unit
:Collective
:Each block:Each group
:Each floor :Not available
1
2
3
4
5
5
Functions
A.
Microsoft®
Internet explorer Ver. 6 or later by Microsoft Corporation is needed.
(Note: You must have "Sun Microsystems Java".)
Microsoft
® Internet explorer is a registered trade mark of Microsoft
Corporation US in the USA and other countries.
B. To gether with integrated centralized control software
TG-2000A, and/or PLC, many optional functions like
"Charging", "Peak-cut", "Energy saving", "General
equipment management", "Scheduling" etc, can be
carried out. Details, please refer to sections of
TG-2000A and PLC software.
C. One AG-150A can control maximum 50 Indoor units
(including LOSSNAY). The integrated centralized
control software TG-2000A can manage maximum
40 AG-150As, therefore can manage maximum
2000 Indoor units (including LOSSNAY).
D.
E.
Taking advantage of AG-150A's Web functions,
alarming E-mail containing address and error code
can be sent to appointed E-mail address upon any
fault happen at the air conditioner system.
AG-150A features a 9"-wide color LCD touch panel.
The settings for air conditioning units can be
changed by touching the corresponding icons on
the display.
External dimension
Unit:mm[in.]
The centralized controller of AG-150A combines Web
function (optional), which enable the air conditioner
system management on a PC browser screen.
*1The management can even carried out remotely.
CENTRALIZED CONTROLLER AG-150A
250 (9-7/8)
146 (5-3/4)
167 (6-5/8)
185 (7-5/16)
272 (10-3/4)
272 (10-3/4)
300 (11-13/16)
44.7
(1-13/16)
25.6
(1-1/16)
Back View
Switches between Cool / Dry / Auto / Fan / Heat. (Group of
LOSSNAY unit : automatic ventilation/ vent - heat interchange/
normal ventilation)
Operation modes vary depending on the air conditioner unit.
Auto mode is the City Multi R2 and WR2 series only.
Range of temperature setting
Weekly schedule can be set for each group of air conditioning units.
2 By registering a license for AG-150A, weekly (2 types), annual, and current day
scheduling function become available.
The system follows either the current day, annual schedule, or weekly, which are
in the descending order of overriding priority.
Twenty-four events can be scheduled per day, including Start/Stop, Mode,
Te mperature Setting, Operation Prohibition, Vane Direction, and Fan Speed.
Two types of weekly schedule (Summer/Winter) can be set.
Settable items dependant on the indoor unit model.
Individually prohibit operation of each local remote control
function (Start/Stop, Change operation mode, Set temperature,
Reset filter).
3: When the local remote controller inactivation command is
received from the master system controller,
"Disabled"appears in inverted display on the operation setting screen.
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
4: When an error occurs, the "ON/OFF" LED flashes. The
operation monitor screen shows the abnormal unit by flashing
it. The error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit address,
error code and source of detection.
The interlocked system settings can be performed by the master
system controller.
When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".
By using accessory cables you can set and monitor the following.
Input: By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local remote
controller"
Output: "Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.
Range of temperature settings vary depending on model.
Cool/Dry:
Heat
:
Auto :
( ) when using middle-temperature on PDFY, PEFY-NMSU/NMHU-by setting DipSW7-1
to ON.
Note: Connect AG-150A to a private network.
290.8(11-1/2)
Installation plate
200(7-7/8)
175.8(6-15/16)
147(5-13/16)
273(10-3/4)
250(9-7/8)
163.4(6-7/16)
167(6-5/8)
261(10-5/16)
3-6. Central controller [AG-150A]
3. SYSTEM CONTROLLER