User`s manual
(66/n)
LEN130391
10.
(1)
(2)
Test Mode
ME96 has the test mode which the fixed values are replied even if the voltage and current are not input. It
can be used to check the communication to programmable controller.
10.1 ME96SSH-MB/ME96SSR-MB
Shift to Test Mode
Operation of ME96 is necessary. At first, shifts to the setting value confirmation mode from the
operation mode. And then, select “9” of menu number, and shifts to the test menu screen. And then,
select “1” of menu number, and shifts to the test mode. (For details, refer to each user’s manual)
How to Test
In the test mode, you need to appear values which wanted to monitor on the screen of ME96. For
example, if you want to monitor the active power, you need to appear the active power on the screen
of ME96.
① Replied Data
Values displayed on the screen of ME96 can be monitored by CC-Link communication. Measurement
elements not displayed on the screen are zero (only power factor is 1.000). When DI1 to DI4 are used, it is
also possible to monitor the digital input status.
② Display screen
In the same as the operating mode, items are displayed when making settings such as those for the display
pattern. Maximum and minimum values can be displayed. (Cyclic function is invalid.)
③ Button Operations
Button Operation
[DISPLAY] Display is changed.
[PHASE] Phase is changed.
[MAXMIN] Mode is changed to the maximum/minimum display and the
instantaneous display.
[+], [-] The item expressed with the bar graph is changed. And, harmonics
number is changed when harmonics displayed.
[+]+[-] for 2 seconds The unit of Wh, varh and VAh is changed.
[SET] Test mode is finished and back to test menu screen.