User`s manual

(59/n)
LEN130391
9.4 Device Allocation
Allocation of transmitted device
Items Contents Device No. Note
Station number 1:
Remote input (RX00 to RX7F)
X1000 to X107F
Remote input
(RX)
Station number 2:
Remote input (RX00 to RX7F)
X1080 to X10FF
Set X100 to remote
input(RX) refresh device.
Station number 1:
Remote output (RY00 to RY7F)
Y1000 to Y107F
Remote output
(RY)
Station number 2:
Remote output (RY00 to RY7F)
Y1080 to Y10FF
Set Y100 to remote
output(RY) refresh device.
Station number 1:
Remote register(RWr0 to RWr3)
W0000 to W001F
Remote register
(RWr)
Station number 2:
Remote register (RWr0 to RWr3)
W0020 to W003F
Set W300 to remote
register(RWr) refresh
device.
Station number 1:
Remote register (RWw0 to RWw3)
W1000 to W101F
Remote register
(RWw)
Station number 2:
Remote register (RWw0 to RWw3)
W1020 to W103F
Set W400 to remote
register(RWw) refresh
device.
Link special relay
(SB)
Link special relay of master station
(SB0 to SB01FF)
SB0 to SB01FF
Set SB0 to link special
relay(SB) refresh device.
Link special register
(SW)
Link special register of master station
(SW0 to SW01FF)
SW0 to SW01FF
Set SW0 to link special
register(SW) refresh
device.
Items of sending data
Sending data for monitoring by
command(1H).
D0 to D32
Number of items are
mentioned in section 9.2.
For station number 1: D1000 to D1031
Error code
For station number 2: D1050 to D1081
For station number 1: M0
Station error
For station number 2: M1
0: Normal
1: Data link error occurred
For station number 1: M100 Check of setting
completion flag
For station number 2: M101
To check the OFF.
For station number 1: M150 Check of monitor
pattern setting flag
For station number 2: M151
To check the OFF.
For station number 1: M200
Start of monitoring
For station number 2: M201
For station number 1: M250
Start of received data
For station number 2: M251
For station number 1: M300 Reception of error for
monitoring by pattern
For station number 2: M301
For station number 1: T0 Wait time for clear
error
For station number 2: T1
For station number 1: T50 Start time for monitor
communication
For station number 2: T51
For station number 1: T100 Reception time for
monitoring by pattern
For station number 2: T101
For station number 1: T150 Time out
For station number 2: T151
For the select of station number Z0 Uses Z0 or Z1.
(To be Indexed the timer)
For the flag of remote I/O Z2
For the remote register Z3
For the write device of received data Z4
Index modification
For the flag of monitoring by pattern Z5