User`s manual

Table 7.21 Data Format (8/8)
Data
Data Format
Setting Items
16bit set register1
(51/n)
LEN130
391
<16bit set register 1>
Data
Bit
Content ON(1) OFF(0)
ME96
SSH
ME96
SSR
b16
Reset of all alarm
executed
b17
Reset of all energy(*1) and all max/min
value(*2)
executed
b18
Reset of all max/min value(*2)
executed
b19
Unusable
b20
Unusable
b21
Unusable
b22
Unusable
b23
Unusable
b24
Reset of all digital input (DI) latch
executed
b25
Unusable
b26
Unusable
b27
Unusable
b28
Unusable
b29
Unusable
b30
Reset of all energy(*1)
executed
b31
Unusable
*1: Periodic active energy (period 1/2) are not reset. Active energy (import/export), reactive energy
(import(LEAD/LAG) /export(LEAD/LAG)), apparent energy and operating time are reset.
*2: Maximum value of rolling demand power is not reset.
b15 b8 b7 b0
Format
Index number
Low data
Unused (00H fixed)
High data
Unused (0000H fixed)
High data
b31 b23
b24 b16
Alarm state