3. Configuration Conditions of CC-Link System
3.1 Remote net ver.2 mode, remote net addional mode
A total of 64 remote I/O stations, remote device stations, local stations, standby master stations, or
intelligent device stations can be connected to a single master station.
However, the following conditions must all be satisfied.
Condition 1
{(a+a2+a4+a8)
+(b+b2+b4+b8)×2
+(c+c2+c4+c8)×3
+(d+d2+d4+d8)×4}≦64
Condition 2
[{(a×32)+(a2×32)+(a4×64)+(a8×128)}
+{(b×64)+(b2×96)+(b4×192)+(b8×384)}
+{(c×96)+(c2×160)+(c4×320)+(c8×640)}
+{(d×128)+(d2×224)+(d4×448)+(d8×896)}]
≦8192
Condition 3
[{(a×4)+(a2×8)+(a4×16)+(a8×32)}
+{(b×8)+(b2×16)+(b4×32)+(b8×64)}
+{(c×12)+(c2×24)+(c4×48)+(c8×96)}
+{(d×16)+(d2×32)+(d4×64)+(d8×128)}]
≦2048
a: The total number of ver.1 compatible slave stations that
occupy 1 station, and ver.2 compatible slave stations
that occupy 1 station which are set to “Single”.
b: The total number of ver.1 compatible slave stations that
occupy 2 stations, and ver.2 compatible slave stations
that occupy 2 stations which are set to “Single”.
c: The total number of ver.1 compatible slave stations that
occupy 3 stations, and ver.2 compatible slave stations
that occupy 3 stations which are set to “Single”.
d: The total number of ver.1 compatible slave stations that
occupy 4 stations, and ver.2 compatible slave stations
that occupy 4 stations which are set to “Single”.
a2: The number of ver.2 compatible stations that occupy 1
station which are set to “Double”.
b2: The number of ver.2 compatible stations that occupy 2
stations which are set to “Double”.
c2: The number of ver.2 compatibl
e stations that occupy 3
stations which are set to “Double”.
d2: The number of ver.2 compatible stations that occupy 4
stations which are set to “Double”.
a4: The number of ver.2 compatible stations that occupy 1
station which are set to “Quadruple”.
b4: The number of ver.2 compatible stations that occupy 2
stations which are set to “Quadruple”.
c4: The number of ver.2 compatible stations that occupy 3
stations which are set to “Quadruple”.
d4: The number of ver.2 compatible stations that occupy 4
stations which are set to “Quadruple”.
a8: The number of ver.2 compatible stations that occupy 1
station which are set to “Octuple”.
(ME96 is applied)
b8: The number of ver.2 compatible stations that occupy 2
stations which are set to “Octuple”.
c8: The number of ver.2 compatible stations that occupy 3
stations which are set to “Octuple”.
d8: The number of ver.2 compatible stations that occupy 4
stations which are set to “Octuple”.
Condition 4
{(16×A) + (54×B) + (88×C)} ≦ 2304
A: Number of remote I/O stations ≦64
B: Number of remote device stations (ME96 is applied)
≦42
C: Number of local stations, standby master stations and
intelligent device stations ≦26