Table 7.19 Data Format (6/8)
Data
Data Format
Setting Items
Phase wiring,
Time constant for
current demand,
Interval time,
Subinterval time
etc.
<Data(Numerical value)>
1) Phase wiring
Setting data Data Note.
Single phase 2 wire (1P2W) 00000001H
Single phase 3 wire (1P3W)(1N3 display) 00000002H
Three phase 3 wire (3P3W_2CT) 00000003H
Three phase 4 wire (3P4W) 00000004H
Single phase 3 wire (1P3W)(1N2 display) 00000005H
Three phase 3 wire (3P3W_3CT) 00000006H
2) Time constant for current demand
Example Data Note.
2 minutes = 120 seconds 00000078H
3) Interval time / Subinterval time
Example Data Note.
15 minutes 0000000FH
4) Byte monitor
Model Data Note.
ME96SSH-MB/ME96SSR-MB C50A 0500H
(49/n)
LEN130391
5) Attribute m
onitor
Model Data Note.
ME96SSH-MB/ME96SSR-MB C510 1000H
6) Model code
Example Data Note.
ME96SSH-MB 00000014H
ME96SSR-MB 00000013H
b15 b8 b7 b0
Format
Index number
Low data
High data
Unused (00H fixed)
High data
b31
b24
b23
b16
b15
b8
b7
b0
Numerical value
Low data
Numerical value: 32-bit integer with a sign
-2147483648 to 2147483647
80000000H to 7FFFFFFFH