User`s manual
Table 7.19 Data Format (6/8)
Data
Data Format ⑥
Setting Items
Phase wiring,
Time constant for
current demand,
Interval time,
Subinterval time
etc.
<Data(Numerical value)>
1) Phase wiring
Setting data Data Note.
Single phase 2 wire (1P2W) 00000001H
Single phase 3 wire (1P3W)(1N3 display) 00000002H
Three phase 3 wire (3P3W_2CT) 00000003H
Three phase 4 wire (3P4W) 00000004H
Single phase 3 wire (1P3W)(1N2 display) 00000005H
Three phase 3 wire (3P3W_3CT) 00000006H
2) Time constant for current demand
Example Data Note.
2 minutes = 120 seconds 00000078H
3) Interval time / Subinterval time
Example Data Note.
15 minutes 0000000FH
4) Byte monitor
Model Data Note.
ME96SSH-MB/ME96SSR-MB C50A 0500H
(49/n)
LEN130391
5) Attribute m
onitor
Model Data Note.
ME96SSH-MB/ME96SSR-MB C510 1000H
6) Model code
Example Data Note.
ME96SSH-MB 00000014H
ME96SSR-MB 00000013H
b15 b8 b7 b0
Format⑥
Index number
Low data
High data
Unused (00H fixed)
High data
b31
b24
b23
b16
b15
b8
b7
b0
Numerical value
Low data
Numerical value: 32-bit integer with a sign
-2147483648 to 2147483647
(80000000H to 7FFFFFFFH)