User`s manual
Table 7.18 Data Format (5/8)
Data
Data Format ⑤
Setting Items
Primary current,
Primary Voltage,
Secondary current,
(48/n)
LEN130391
Seco
ndary Voltage,
Frequency,
etc.
<Multiplying factor>
Multiplying factor is fixed according to setting of the phase wiring, primary voltage and primary current.
(Refer to 7.2.5).
Inde
x number = 00H: The actual value is the numeric value.
Index number = FFH: The actual value is 10
-1
times the numeric value
<Example: Primary current >
Setting data Multiplying factor Numerical value Actual value
Setting data = 100.0A x10
-1
⇒FFH 1000⇒03E8H FF000003E8H
Setting data = 400A x1
⇒00H 400⇒0190H 0000000190H
<Example: Primary voltage>
Setting data Multiplying factor Numerical value Actual value
Setting data = 110.0V x10
-1
⇒FFH 1100⇒044CH FF0000044CH
Setting data = 3300V x1
⇒00H 3300⇒0CE4H 0000000CE4H
b15 b8 b7 b0
Format⑤
Index number
Low data
High data
Multiplying factor
Numerical value
High data
b31
b24
b23
b16
b15
b8
b7
b0
Low data
Numerical value: 32-bit integer with a sign
-2147483648 to 2147483647
(80000000H to 7FFFFFFFH)