Table 7.15 Data Format (2/8)
Data
Data Format
Measurement
Items
(44/n)
LEN130391
Active energy,
Reactive energy,
Apparent energy,
Operation time,
etc.
Multiplying factor
Multiplying factor is fixed according to settings of primary current, primary voltage, and phase
wire system. (Refer to 7.2.5.)
Index number Multiplying factor Remarks
03H x10
3
02H x10
2
01H x10
00H x1
FFH x10
-1
FEH x10
-2
FDH x10
-3
FCH x10
-4
FBH x10
-5
Actual value =
Numerical value
× Multiplying factor
Example: Active Energy
Data Multiplying
factor
Numerical value Actual value
FF000000FFH FFHx10
-1
000000FFH255 255x10
-1
= 25.5[kWh]
00000000FFH 00Hx1 000000FFH255 255x1 = 255[kWh]
Note: For active energy (export), reactive energy (export/Lag) and reactive energy
(export/Lead), the reply data are unsigned although the display of main device has a
“-“(negative) sign.
b15 b8 b7 b0
Multiplying
Index number
Format
Low data
High data
High data
b31
b24
b23
b16
b15
b8
b7
b0
Numerical value: 32-bit integer with a sign
However, the effective numerical value is 0 to 999999(0H to F423FH)
Data changes 999998 999999 0 1 .
(Operation time stops at 999999.)
Low data
Numeric
al value