User`s manual

(42/n)
LEN130391
3P3W or 1P2W
Set a direct voltage value (Ex. 110V, 220V etc.).
It is set “Direct input”, and set the primary voltage which is transmitted as the direct input voltage.
Set within the range of from 60V to 750000V.
It is set “Using VT”, and set the primary voltage which is transmitted. From the most significant digit to 3
figures can be freely set up in the range.
1P3W
110V or 220V is valid only.
*3: Effective value of primary voltage(L-N) is follows.
3P4W
Set a direct voltage value (Ex. 63.5V, 100V, 110V, 220V, 240V, 254V or 277V)
It is set “Direct input”, and set the primary voltage which is transmitted as the direct input voltage.
Set within the range from 60V to 750000V.
It is set “Using VT”, and set the primary voltage which is transmitted. From the most significant digit to 3
figures can be freely set up in the range.
3P3W, 1P3W or 1P2W
It is unsupported. Use the primary voltage value (L-L) (*2).
*4: Effective value of secondary voltage is follows.
3P4W, 3P3W or 1P2W
About setting range, please refer to each user’s manuals.
In case of 3P4W, set the voltage of L-N. In case of 3P3W, set the voltage of L-L. If the setting of ME96 is
“Direct voltage”, the setting is changed “With VT” and set the secondary voltage. Furthermore, the setting
of the primary voltage is changed to the initial value or the previous value.
1P3W
It is unsupported.
*5: The set value is the second unit value. (For example of 2 miniutes, sets as 120 seconds.) About setting range,
please refer to each user’s manuals.
*6: When the interval time constant is changed, the subinterval time constant is changed to 1 min. When the
subinterval is changed, if the interval time constant cannot be divided by subinterval time constant, it will be the
error of illegal data value.
*7: Multiplying factor differs according to settings of phase wiring, primary voltage and primary current. For details,
refer to.
7.2.5.
*8:
About setting of upper/lower limit value.
About setting range, please refer to each users manuals.
Setting of upper/lower limit value is not a percentage value of maximum scale but a direct value.
(In case of current harmonic and phase N current harmonic, use a percentage value for the maximum
scale.)
When the setting value is other than setting step, it is rounded according to following calculation.
Calculate: Setting value via CC-Link / maximum scale (±0step) x 100 Rounds to the whole number.
Example: In case of setting value is 55.5kW, maximum scale (±0step) is 100kW.
55.5kW / 100kW x100 = 55.5% 56%
When out of range is set, the error code of invalid data is replied, and setting value is not changed.
If the upper/lower limit value of W, DW and var exceeds
±1638.3MW(Mvar), please set by the main
device.