Table 7.13 List of Group and Channel for Setting
ME96SSH-MB ME96SSR-MB
Group
(h)
Channel
(h)
Name of Cannel Setting range
3P4W
3P3W
1P3W
1P2W 3P4W
3P3W
1P3W
1P2W
Data
type
Note
E0 11 Primary current 1.0A to 30000.0A
○○○○ ○ ○ ⑤
*1
E0 12 Primary voltage(L-L)
60V~750000V ○○○○ ○ ○ ⑤
*2
E0 1B Primary voltage(L-N)
60V~750000V ○- -○ - - ⑤
*3
E0 1C Scondary voltage (Refer to *4)
○○○○ ○ ○ ⑤
*4
E0 13 Phase wiring
Refer to data type ⑥ ○○○○ ○ ○ ⑥
E0 1D Frequency 50Hz, 60Hz
○○○○ ○ ○ ⑤
E0 1E Secondary current 5A, 1A
○○○○ ○ ○ ⑤
E0 18 Alarm items
Refer to data type ⑦ ○○○○ ○ ○ ⑦
02 E0 Time constant for current demand 0 to 1800 sec.
○○○○ ○ ○ ⑥
*5
08 E4 Interval time constant 1 to 60 min
○○○ - - - ⑥
*6
08 E5 Subinterval time constant 1 to 60 min
○○○ - - - ⑥
*6
80 01 Active energy import 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
80 63 Active energy export 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
81 01 Reactive energy import lag 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
81 63 Reactive energy export lag 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
81 64 Reactive energy import lead 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
81 65 Reactive energy export lead 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
82 01 Apparent energy 0 to 999999 x Multiplying
○- - - - - ②
*7
8B 01 Periodic active energy(Period 1) 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
8C 01 Periodic active energy(Period 2) 0 to 999999 x Multiplying
○○○○ ○ ○ ②
*7
01 14 Current upper limit 5 to 120% (1% step)
○○○○ ○ ○ ①
*8
01 15 Current lower limit 3 to 95% (1% step)
○○○○ ○ ○ ①
*8
01 94 Current upper limit(Phase N) 5 to 120% (1% step)
○- -○ - - ①
*8
02 14 Current demand upper limit 5 to 120% (1% step)
○○○○ ○ ○ ①
*8
02 15 Current demand lower limit 3 to 95% (1% step)
○○○○ ○ ○ ①
*8
02 94
Current demand upper limit
(Phase N)
5 to 120% (1% step)
○- -○ - -
①
*8
05 14
Voltage upper limit(L-L)
25 to 135% (1% step)
○○○○ ○ ○ ①
*8
05 15
Voltage lower limit(L-L)
20 to 95% (1% step)
○○○○ ○ ○ ①
*8
03 14
Voltage upper limit(L-N)
25 to 135% (1% step)
○○○○ ○ ○ ①
*8
03 15
Voltage lower limit(L-N)
20 to 95% (1% step)
○○○○ ○ ○ ①
*8
07 14 Active power upper limit -95 to 120% (1% step)
○○○○ ○ ○ ①
*8
07 15 Active power lower limit -120 to 95% (1% step)
○○○○ ○ ○ ①
*8
08 14 Rolling demand upper limit 5 to 120% (1% step)
○○○ - - - ①
*8
09 14 Reactive power upper limit -95 to 120% (1% step)
○○○○ ○ ○ ①
*8
09 15 Reactive power lower limit -120 to 95% (1% step)
○○○○ ○ ○ ①
*8
0D 14 Power factor upper limit
-0.05 to 1 to 0.05
(0.05 step)
○○○○ ○ ○
①
*8
0D 15 Power factor lower limit
-0.05 to 1 to 0.05
(0.05 step)
○○○○ ○ ○
①
*8
0F 14 Frequency upper limit 45 to 65Hz (1Hz step)
○○○○ ○ ○ ①
*8
0F 15 Frequency lower limit 45 to 65Hz (1Hz step)
○○○○ ○ ○ ①
*8
77 E1 H.V(L-N) upper limit 0.5 to 20% (0.5% step)
○○○○ ○ ○ ①
*8
76 E1 H.V(L-L) upper limit 0.5 to 20% (0.5% step)
○○○○ ○ ○ ①
*8
75 E1 H.A upper limit 1 to 120% (1% step)
○○○○ ○ ○ ①
*8
75 F1 H.A upper limit(Phase N) 1 to 120% (1% step)
○- -○ - - ①
*8
A1 3A 16bit set register 1
Refer to data type ⑧ ○○○○ ○ ○ ⑧
A1 3B 16bit set register 2
Refer to data type ⑧ ○○○○ ○ ○ ⑧
*1: From the most significant digit to 3 digits can be freely setting in the range. Digits of 4 or more are rounded down
to 3 digits. (When less than 10A, to 2 digits.)
In details of setting data and setting ranges, please refer each user’s manuals.
*2: Effective value of primary voltage(L-L) is follows.
3P4W
It is valid only 190V, 415V, 440V. And it changed as follows by set value.
Set value
Using VT/
Direct input
Direct voltage
VT secondary
voltage
VT primary voltage
190V Direct input 110V/190V ― ―
415V Using VT ― 63.5V/110V 240V/415V
440V Using VT ― 63.5V/110V 254V/440V