User`s manual
7.2.3 When Setting by Command(2H)
Settings of ME96 can be set by communication.
Monitor pattern setting flag(RX(n+1)0) is used to send the command. (For details, refer to section
6.4.2)
The comma
nd can be sent only when the remote READY(RX(n+7)B) is ON.
(40/n)
LEN130391
Remote register RWw(ME96→Programmable controller)
b15 b8 b7 b0
RWw00
Group No.
0H
2H
RWw01
Index number Channel No.
RWw02
Low data
RWw03
High data
RWw04
00H 00H
RWw05
00H 00H
RWw06
00H 00H
RWw07
00H 00H
to to
RWw1C
00H 00H
RWw1D
00H 00H
RWw1E
00H 00H
RWw1F
00H 00H
Remote register RWw(Programmable controller→ME96)
2H
Data Set
b15 b8 b7 b0
Channel No. Group No.
RWr00
00H (Error
code)
RWr01
00H 00H
RWr02
00H 00H
RWr03
00H 00H
RWr04
00H 00H
RWr05
00H 00H
RWr06
00H 00H
RWr07
to to
00H 00H
RWr1C
00H 00H
RWr1D
00H 00H
RWr1E
00H 00H
RWr1F
* At normal communication, Error code is 00h.
About the other error code, refer to Table 7.23.
*
At data set
,
Unit No. is fixed 0H in ME96.
・ A setting item of ME96 can be set by storing Group No., Channel No. and setting data to remote register(RWw).
・ About Group No. and Channel No., refer to Table 7.2 to Table 7.12)
・ The details of data format are shown in the Table 7.14 to Table 7.21
* After writing the set-up value, about 2 seconds ( max 4 seconds) is needed to restart the measurement based on new
set-up value.