User`s manual

(39/n)
LEN130391
Table 7.12 Group Channel List (11/11)
ME96SSH-MB ME96SSR-MB
Unit
No.
Group
(h)
Channel
(h)
Name of Cannel
3P4W
3P3W
1P3W
1P2W 3P4W
3P3W
1P3W
1P2W
Data
type
Note
0 01 14 Current upper limit A Alarm
○○○○
0 01 15 Current lower limit A Alarm
○○○○
0 01 94 Current upper limit A Alarm PhaseN
○- -○ - -
0 02 14 Current demand upper limit A Alarm
○○○○
0 02 15 Current demand lower limit A Alarm
○○○○
0 02 94 Current demand upper limit A Alarm PhaseN
○- -○ - -
0 05 14
Voltage upper limitL-L
V Alarm
○○○○
0 05 15
Voltage lower limitL-L
V Alarm
○○○○
0 03 14
Voltage upper limitL-N
V Alarm
○○○○
0 03 15
Voltage lower limitL-N
V Alarm
○○○○
0 07 14 Active power upper limit kW Alarm
○○○○
0 07 15 Active power lower limit kW Alarm
○○○○
0 08 14 Rolling demand upper limit kW Alarm
○○ - - -
0 09 14 Reactive power upper limit kvar Alarm
○○○○
0 09 15 Reactive power lower limit kvar Alarm
○○○○
0 0D 14 Power factor upper limit % Alarm
○○○○
0 0D 15 Power factor lower limit % Alarm
○○○○
0 0F 14 Frequency upper limit Hz Alarm
○○○○
0 0F 15 Frequency lower limit Hz Alarm
○○○○
0 77 E1 H.V(L-N) upper limit % Alarm Total
○○○○
0 76 E1 H.V(L-L) upper limit % Alarm Total
○○○○
0 75 E1 H.A upper limit A Alarm Total
○○○○
0 75 F1 H.A upper limit(Phase N) A Alarm Total
○- -○ - -
0 A0 31 Alarm state Alarm
○○○○
0 A0 35 Alarm state2 Alarm
○○○○
Inst.: Instantaneous value, max.: maximum value, min.: minimum value.
*1: in the table means that it is applicable when the setting of phase wiring is 3P3W_3CT only.
*2: Unit number is “0” when the setting of phase wiring is 1P2W, 1P3W or 3P3W.
*3: About the reply data of active energy(Wh), reactive energy(varh) and apparent energy(VAh), refer to follows.
Example) In case of active energy(import) data is 876,543,210,987,654,321mWh, each reply data are follows.
GWh MWh kWh Wh mWh
Data=87654321 0 9 8 7 6 54321
Unit
No.
Group
(h)
Chann
el (h)
Name of Cannel Total power[kW] Note
less than 10 0 9 8 7 6 5
10 or more and less than 100 1 0 9 8 7 6
100 or more and less than 1000 2 1 0 9 8 7
1000 or more and less than 10000 3 2 1 0 9 8
10000 or more and less than 100000 4 3 2 1 0 9
0 80 01 Active energy import
100000 or more 5 4 3 2 1 0
less than 10 7 6 5432
10 or more and less than 100 8 7 6 5 4 3
100 or more and less than 1000 9 8 7 6 5 4
1000 or more and less than 10000 0 9 8 7 6 5
10000 or more and less than 100000 1 0 9 8 7 6
0 80 64
Active energy import
(expand)
100000 or more 2 1 0 9 8 7
*1
1 B0 01
Active energy import
(unit fixed: Wh)
- 2 1 0 9 8 7 6 5 4
1 B0 02
Active energy import
(unit fixed: kWh)
- 5 4 3 2 1 0 9 8 7
1 B0 03
Active energy import
(unit fixed: MWh)
- 87654321 0
*2
*1: The data of energy wil change according to the total load setting of ME96. (This matches to display of ME96NSR.) Multiplying the
receving data by the multiplying factor of section gives the actual value (unit:kWh).
*2: The data of energy of selected unit will reply regardless to the total load setting of ME96. (This matches to the additional display(9
digits) of ME96SSH/ME96SSR.