(2) Group format
For group format , Up to 16 measuring items can be monitored per a group. Measuring items are
expressed in 2 words. However, it is necessary to be multiplied by using Table 7.22 because there is
no multiplying
factor data .
Group format
b15 b8 b7 b0
RWr00 Low data
RWr01 High data
RWr02 Low data
RWr03 High data
RWr04 Low data
RWr05 High data
RWr06 Low data
RWr07 High data
RWr08 Low data
RWr09 High data
RWr0A Low data
RWr0B High data
RWr0C Low data
RWr0D High data
RWr0E Low data
RWr0F High data
RWr10 Low data
RWr11 High data
RWr12 Low data
RWr13 High data
RWr14 Low data
RWr15 High data
RWr16 Low data
RWr17 High data
RWr18 Low data
RWr19 High data
RWr1A Low data
RWr1B High data
RWr1C Low data
RWr1D High data
RWr1E Low data
RWr1F High data
<Numerical value>
High data
b31
b24
b23
b16
b15
b8
b7
b0
Low data
Numeric
al value: 32-bit integer with a sign
-21474836482147483647
80000000H7FFFFFFFH
F
ormat of numerical value is same to group format .
This format is not contain multiplying factor data.
Therefore, Confirm the multiplying factor fixed according to
phase wire system, primary voltage and primary current by
Table 7.22, and multiply it using sequence program.
Example: Phase 1 current
When setting of primary current is 200A, multiplying factor
is ×10
-1
according to section Table 7.22.
Data(Numerical value) Actual value
255×10
-1
25.5[A] 000000FFH 255
Example: Active power
When settings are follows, multiplying factor is ×10
according to section Table 7.22.
Phase wire system: 3P4W
Primary voltage: 254/440V
Primary current: 2000A
Total load = 3 × 254 × 2000 / 1000 = 1524[kW]
Data(Numerical value) Actual value
0000FFFFH 65535 65535×10655350[kWh]