User`s manual
(1) Group format ①
For group format ①, Up to 8 measuring items can be monitored per a group. Measuring items are
expressed in 4 words.
Group format ①
b15 b8 b7 b0
RWr00 Channel No. Group No.
(26/n)
LEN130391
RWr01 Index number 00h
RWr02 Low data
RWr03 High data
RWr04 Channel No. Group No.
RWr05 Index number 00h
RWr06 Low data
RWr07 High data
RWr08 Channel No. Group No.
RWr09 Index number 00h
RWr0A Low data
RWr0B High data
RWr0C Channel No. Group No.
RWr0D Index number 00h
RWr0E Low data
RWr0F High data
RWr10 Channel No. Group No.
RWr11 Index number 00h
RWr12 Low data
RWr13 High data
RWr14 Channel No. Group No.
RWr15 Index number 00h
RWr16 Low data
RWr17 High data
RWr18 Channel No. Group No.
RWr19 Index number 00h
RWr1A Low data
RWr1B High data
RWr1C Channel No. Group No.
RWr1D Index number 00h
RWr1E Low data
RWr1F High data
<Channel No., Group No.>
ME96 returns fixed data determined for each
measuring items. (About fixed data, refer to Table
7.2 to Table 7.12)
(Example:When selected phase 1 current (Inst),
channel No.is 21h, group No. is 01h.)
<Multiplying factor>
Multiplying factor is fixed for each items according to
phase wire system, primary voltage and primary
current.(For details, refer to Table 7.22)
■Correspondence of index number and multiplying
factor.
Index
number
Multiplying
factor
Remarks
02H ×10
2
01H ×10
00H ×1
FFH ×10
-1
FEH ×10
-2
FDH ×10
-3
FCH ×10
-4
Actual value =
Numerical value
× Multiplying factor
<Numerical value>
High data
b31
b24
b23
b16
b15
b8
b7
b0
Low data
Numeric
al value: 32-bit integer with a sign
-2147483648~2147483647
(80000000H~7FFFFFFFH)
■Examp
le: Active power
Index Data
Actual value
number (Numerical value)
255×10
-1
=25.5[kW] FFH 000000FFH ⇒ 255
00H FFFFFF01H ⇒ -255 -255×1=-255[kW]
■Example: power factor
Index Data
Actual value
number (Numerical value)
995×10
-1
=99.5[%] FFH 000003E3H ⇒ 995
-995×10
-1
=-99.5[%] FFH FFFFFC1DH⇒ -995