7.2.1 When Monitoring by Pattern
The following table shows correspondence between RY and grouped measuring items.
Table 7.1 Correspondence between RY and grouped measuring items
P08 P09 P10 P11 P12
device.
RY(n+1)8 RY(n+1)9 RY(n+1)A RY(n+1)B RY(n+1)C
RWr00
RWr01
Phase 1 current
(Inst.)[A]
Phase N current
(Inst.)[A]
RWr02
RWr03
Phase 1 current
(Inst.)[A]
Phase 1 current
demand (Inst.)[A]
Phase N current
(Inst.)[A]
Phase 2 current
(Inst.)[A]
Phase N current
demand (Inst.)[A]
RWr04
RWr05
Phase 3 current
(Inst.)[A]
1-N Voltage
(Inst.)[V]
RWr06
RWr07
Phase 2 current
(Inst.)[A]
Phase 2 current
demand (Inst.)[A]
Phase N current
demand (Inst.)[A]
Phase 1 current
demand (Inst.)[A]
2-N Voltage
(Inst.)[V]
RWr08
RWr09
Phase 2 current
demand (Inst.)[A]
3-N Voltage
(Inst.)[V]
RWr0A
RWr0B
Phase 3 current
(Inst.)[A]
Phase 3 current
demand (Inst.)[A]
1-N Voltage
(Inst.)[V]
Phase 3 current
demand (Inst.)[A]
Average current
(Inst.)[A]
RWr0C
RWr0D
1-2 Voltage
(Inst.)[V]
Avrage current
demand (Inst.)[A]
RWr0E
RWr0F
1-2 Voltage
(Inst.)[V]
Total rolling demand
(Inst.)[kW] *1
2-N Voltage
(Inst.)[V]
2-3 Voltage
(Inst.)[V]
Average L-L
voltage (Inst.)[V]
RWr10
RWr11
3-1 Voltage
(Inst.)[V]
Average L-N
voltage (Inst.)[V]
RWr12
RWr13
2-3 Voltage
(Inst.)[V]
Total power factor
(Inst.)[%]
3-N Voltage
(Inst.)[V]
Total active power
(Inst.)[kW]
00h
(No items)
RWr14
RWr15
Total rolling demand
(Inst.)[kW] *1
00h
(No items)
RWr16
RWr17
3-1 Voltage
(Inst.)[V]
Frequency
(Inst.)[Hz]
00h
(No items)
Total reactive power
(Inst.)[kvar]
00h
(No items)
RWr18
RWr19
Total power factor
(Inst.)[%]
00h
(No items)
RWr1A
RWr1B
Total active power
(Inst.)[kW]
Total reactive power
(Inst.)[kvar]
00h
(No items)
Frequency
(Inst.)[Hz]
00h
(No items)
RWr1C
RWr1D
Active energy
import[kWh]
00h
(No items)
RWr1E
RWr1F
Active energy
import[kWh]
Reactive energy
import lag [kvarh]
00h
(No items)
Reactive energy
import lag [kvarh]
00h
(No items)
Group
format
① ① ① ② ②
Inst.: Instantaneous value
*1: ME96SSH-MB Only.
Note: “[ ]” in the above table indicate the unit of measuring items.
Note: P10 and P12 can be used for 3P4W only. In others, the error will occur.
Note: For the active power (demand) and reactive power,
±1638.3MW(Mvar) becomes the upper(lower) value.
Note: For the power factor, “+” is showed lag, “-“ is showed lead as with ME96’s display.
Note: Measurement data correspond as follows according to setting of phase wiring.
Phase wiring
Name of channel
3P3W 1P3W(1N3) 1P3W(1N2) 1P2W
1-2 voltage 1-2 voltage 1-N voltage 1-N voltage Voltage
2-3 voltage 2-3 voltage 3-N voltage 2-N voltage -
3-1 voltage 3-1 voltage 1-3 voltage 1-3 voltage -
Phase 1 current Phase 1 current Phase 1 current Phase 1 current Current
Phase 2 current Phase 2 current Phase N current Phase N current -
Phase 3 current Phase 3 current Phase 3 current Phase 2 current -