User`s manual
(1) Relationships between programmable controller CPU, master module and ME96(RWr)
1) The remote registers RWr data of a remote device station is automatically stored in the "remote
registers Rwr" buffer memory of the master station.
1) The remote registers RWr data of a remote device station is automatically stored in the "remote
registers Rwr" buffer memory of the master station.
2) The remote registers RWr data of ME96 stored in the "remote registers RWr" buffer memory is
stored in the CPU device set with the automatic refresh parameters.
2) The remote registers RWr data of ME96 stored in the "remote registers RWr" buffer memory is
stored in the CPU device set with the automatic refresh parameters.
1) Relationships between programmable controller CPU, master module and ME96(RWr)
Programmable controller CPU
Master module ME96(Station number 1)
(23/n)
LEN130391
Station Station
number number
Device No. Device No.
StationStation
numbernumber
Device No. Device No.
Station Station
number number
Device No. Device No.
1 W0000 to W001F 15 W01C0 to W01DF 29 W0380 to W039F
2 W0020 to W003F 16 W01E0 to W01FF 30 W03A0 to W03BF
3 W0040 to W005F 17 W0200 to W021F 31 W03C0 to W03DF
4 W0060 to W007F 18 W0220 to W023F 32 W03E0 to W03FF
5 W0080 to W009F 19 W0240 to W025F 33 W0400 to W041F
6 W00A0 to W00BF 20 W0260 to W027F 34 W0420 to W043F
7 W00C0 to W00DF 21 W0280 to W029F 35 W0440 to W045F
8 W00E0 to W00FF 22 W02A0 to W02BF 36 W0460 to W047F
9 W0100 to W011F 23 W02C0 to W02DF 37 W0480 to W049F
10 W0120 to W013F 24 W02E0 to W02FF 38 W04A0 to W04BF
11 W0140 to W015F 25 W0300 to W031F 39 W04C0 to W04DF
12 W0160 to W017F 26 W0320 to W033F 40 W04E0 to W04FF
13 W0180 to W019F 27 W0340 to W035F 41 W0500 to W051F
14 W01A0 to W01BF 28 W0360 to W037F 42 W0520 to W053F
Device No. is determined to “W0000 to W053F” if refresh device of remote registers (RWr) is set to “W0”.
Device No.
W0000
ME96 W0001
(Station number1) to
W001E
W001F
W0020
ME96 W0021
(Station number2) to
W003E
W003F
to
W0520
ME96 W0521
(Station number42) to
W053E
W053F
Remote register(RWr)
Remote register(RWr)
RWr00
RWr00
RWr01
RWr01
to
RWr1E
RWr1F
RWr20
RWr21
to
RWr3E
RWr3F
to
RWr520
RWr521
to
RWr53E
RWr53F
to
RWr1E
RWr1F
ME96(Station number 2)
ME96(Station number 42)
to
Remote register(RWr)
RWr00
RWr01
to
RWr1E
RWr1F
Remote register(RWr)
RWr00
RWr01
to
RWr1E
RWr1F
2) 1)
1)2)
2) 1)