User`s manual

(1) Relationships between programmable controller CPU, master module and ME96(RY)
1) The on/off data of the CPU device set with the automatic refresh parameters is stored in the
"remote output RY" buffer memory.
1) The on/off data of the CPU device set with the automatic refresh parameters is stored in the
"remote output RY" buffer memory.
2) Remote output RY is automatically set to on/off (for each link scan) according to the output status
stored in the "remote output RY" buffer memory.
2) Remote output RY is automatically set to on/off (for each link scan) according to the output status
stored in the "remote output RY" buffer memory.
1) Relationships between programmable controller CPU, master module and ME96(RY)
Programmable controller CPU
Master module ME96(Station number 1)
(21/n)
LEN130391
Station Station
number number
Device No. Device No.
StationStation
numbernumber
Device No. Device No.
StationStation
numbernumber
Device No. Device No.
1 Y1000 to Y107F 15 Y1700 to Y177F 29 Y1E00 to Y1E7F
2 Y1080 to Y10FF 16 Y1780 to Y17FF 30 Y1E80 to Y1EFF
3 Y1100 to Y117F 17 Y1800 to Y187F 31 Y1F00 to Y1F7F
4 Y1180 to Y11FF 18 Y1880 to Y18FF 32 Y1F80 to Y1FFF
5 Y1200 to Y127F 19 Y1900 to Y197F 33 Y2000 to Y207F
6 Y1280 to Y12FF 20 Y1980 to Y19FF 34 Y2080 to Y20FF
7 Y1300 to Y137F 21 Y1A00 to Y1A7F 35 Y2100 to Y217F
8 Y1380 to Y13FF 22 Y1A80 to Y1AFF 36 Y2180 to Y21FF
9 Y1400 to Y147F 23 Y1B00 to Y1B7F 37 Y2200 to Y227F
10 Y1480 to Y14FF 24 Y1B80 to Y1BFF 38 Y2280 to Y22FF
11 Y1500 to Y157F 25 Y1C00 to Y1C7F 39 Y2300 to Y237F
12 Y1580 to Y15FF 26 Y1C80 to Y1CFF 40 Y2380 to Y23FF
13 Y1600 to Y167F 27 Y1D00 to Y1D7F 41 Y2400 to Y247F
14 Y1680 to Y16FF 28 Y1D80 to Y1DFF 42 Y2480 to Y24FF
Device No. is determined to “Y1000 to Y24FF” if refresh device of remote output (RY) is set to “Y1000”.
Device Y
Y1000 to Y100F
Y1010 to Y101F
Y1020 to Y102F
ME96 Y1030 to Y103F
(Station number1) Y1040 to Y104F
Y1050 to Y105F
Y1060 to Y106F
Y1070 to Y107F
ME96 Y1000 to Y100F
(Station number2) to
Y10F0 to Y10FF
to
ME96 Y2480 to Y248F
(Station number42) to
Y24F0 to Y24FF
Remote output(RY)
Remote output(RY)
R
Y00 to RY0F
RY10 to RY1F
RY20 to RY2F
RY30 to RY3F
RY40 to RY4F
RY50 to RY5F
RY60 to RY6F
RY70 to RY7F
RY80 to RY8F
RY00 to RY0F
RY10 to RY1F
RY20 to RY2F
RYF0 to RYFF
to
RY1480 to RY148F
to
RY14F0 to RY14FF
RY30 to RY3F
2)
RY40 to RY4F
RY50 to RY5F
RY60 to RY6F
RY70 to RY7F
ME96(Station number 2)
Remote output(RY)
RY00 to RY0F
to
RY70 to RY7F
ME96(Station number 42)
to
Remote output(RY)
RY00 to RY0F
to
RY70 to RY7F
1)
1)
2)
1)
2)