User`s manual

(20/n)
LEN130391
7.1.2 Remote Output RY
The allocation of the remote output RY of ME96 is shown in the table below.
Description
Device
No.
Signal name
ON1)→OFF0 OFF0)→ON1
Note
RYn0
to
RYnF
Reserved
RY(n+1)0
Monitor pattern setting flag P00
Not setting Setting
RY(n+1)1
to
RY(n+1)7
Reserved
RY(n+1)8
Monitor pattern setting flag P08
Not setting Setting
RY(n+1)9
Monitor pattern setting flag P09
Not setting Setting
RY(n+1)A
Monitor pattern setting flag P10
Not setting Setting
RY(n+1)B
Monitor pattern setting flag P11
Not setting Setting
RY(n+1)C
Monitor pattern setting flag P12
Not setting Setting
RY(n+1)D
to
RY(n+7)7
Reserved
RY(n+7)8
Initial data
setting completion flag
Cancel normal
communication request
Normal communication
request
*1
RY(n+7)9
Unusable
RY(n+7)A
Error reset request flag
Cancel error reset request Error reset request *1
RY(n+7)B
to
RY(n+7)F
Unusable
*1: For the details, refet to “6.Communication Between the Master Station and ME96
Note:
The “n” in the table is determined by the station number of ME96.
Point
Do not read or write to reserved remote registers. If reading or writing is performed, the
functions of ME96 are not guaranteed.