User`s manual

6.4.3 Setting by Command(2H)
A setting item of ME96 can be set by setting the unique codes (called unit No., group No. and channel
No.) and setting data.
RY(n+1)0
(Monitor pattern
setting flag
=P00)
RX(n+1)0
(Setting
completion frag)
Remote register
Dat
a = 00h
Response data
Writes to
master station
Data = 00h
(R
Wr)
Remote register
(R
Ww)
(1) Setting
Writes the Unit No., group No, channel No. and setting data to remote registers(RWw).
Turns on monitor pattern setting flag(RY(n+1)0).
After checking for data at ME96, corresponding setting completion flag(RX(n+1)0) is turned on. At
this time, response data are stored in remote registers(RWr).
(2) End of setting
Turns off monitor pattern setting flag(RY(n+1)0).
Corresponding setting completion flag(RX(n+1)m) is turned off and remote registers are 00h.
Note: When monitor pattern setting flag(RY(n+1)0) remains on, setting data of ME96 is not reflected if
remote registers(RWw) is changed. To change setting data, turns on monitor pattern setting
flag(RY(n+1)0) after writing remote registers(RWw).
(17/n)