6.4.2 Monitoring by Command(1H)
Up to 8 measuring values can be monitored by setting the unique codes (called unit No., group No. and
channel No.).
(1) Start of monitor
Writes the Unit No., group No and channel No. for measuring items to be monitored to remote
registers(RWw).
Turns on monitor pattern setting flag(RY(n+1)0).
When the measuring values can be monitored with ME96, corresponding setting completion
flag(RX(n+1)0) is turned on. At this time, Measuring values are stored in remote registers(RWr)
each time the measuring data of ME96 is updating.
(2) End of monitor
Turns off monitor pattern setting flag(RY(n+1)0).
Corresponding setting completion flag(RX(n+1)m) is turned off and remote registers are 00h.
Note: When monitor pattern setting flag(RY(n+1)0) remains on, measuring items in remote
registers(RWr) is not reflected if remote registers(RWw) is changed. To change measuring items,
turns on monitor pattern setting flag(RY(n+1)0) after changing remote registers(RWw).