User`s manual
6.4 Normal Communication
After initial data processing is complete, allows the monitoring by pattern, monitoring by command(1H)
and setting by command(2H).
6.4.1 Monitoring by Pattern
Up to 16 mesuring values can be monitored by setting a bit of RY. Measuring values which can be
monitored have been already grouping in ME96 in advance. Therefore, select the necessary group in a
bit of RY. (Refer to section 7.1.2)
RY(n+1)m
(Monitor pattern
setting flag )
RX(n+1)m
(Setting
completion flag)
Remote register
(RWr)
Data = 00h
①
Data is always updating.
Data = 00h
④
④
②
②
③
(1) Start of monitor
①Turns on monitor pattern setting flag(RY(n+1)m) which will be monitored.
②Corresponding setting completion flag(RX(n+1)m) is turned on when the measuring values can be
monitored at ME96. At this time, Measuring values are stored in remote registers(RWr) each time
the measuring data of ME96 is updating.
(2) End of monitor
③Turns off monitor pattern setting flag(RY(n+1)m).
④Corresponding setting completion flag(RX(n+1)m) is turned off and remote registers are 00h.
Note: When turns on multiple monitor pattern setting flag(RY(n+1)*), setting completion flag is not turned
on. At this time, error status flag(RX(n+7)A) is turned on, and remote READY(RX(n+7)B) is turned
off.
(15/n)