User`s manual

(13/n)
LEN130391
6. Communication Between the Master Station and ME96
6.1 Communication Guideline
There are three communication statuses (Initial Communication, Normal Communication, Error
Communication) between the Master station and ME96.
In the normal communication, alarm status and digital input status of ME96 can be monitored using bit
data (remote input RX). Furthermore, the following can be performed by using remote input, remote
output and remote registers.
Monitoring by Pattern
Monitoring by Command(1H).
Setting by Command(2H).
For a monitoring by pattern, some measuring values can be monitored by selecting a bit of RY.
Measuring values which can be monitored have been already grouping in ME96 in advance. Please
select the necessary group in a bit of RY.
For a monitoring by command(1H), you can select any measurement items to be monitored. ME96 has
unique codes (called unit No., group No. and channel No.) for each measurement items. You can monitor
the selected measurement items by writing these codes to the remote registers.
For a setting by command(2H), you can set for ME96 settings.
* All measuring items can be monitored even when it is not displayed in ME96.