(1) For the automatic refresh parameter setting, set the start device only. Devices are
automatically assigned until the last station number including reserved stations and
occupied stations.
In the example of the system configuration in this section, the last station number is "2".
Therefore, total of remote I/O points is 256 points (128 x 2 = 256) and total of remote
registers points is 64 points (32 x 2 = 64). If refresh device of remote input (RX) is set to
"X1000" and that of remote registers (RWr) is set to "W0", the end devices will be
"X10FF" and "W3F" respectively.
(2) When setting X, Y, B, W, SB and SW as refresh devices, make setting so that they do
not overlap with the device numbers used on the other networks, etc.
《Example for Operational settings》
Setting Item Description
Example for
settings
Remarks
Parameter name
Set the Parameter name.
“SAMPLE”
Even if the Parameter
name is not set, this will not affect the
operation of the CC-Link system
Data link disorder
satation setting
Set the input status for the data link
error station.
Clear ("Hold
input data"
not checked)
Case of CPU Stop
setting
Set the slave station
refresh/compulsory clear setting at
programmable controller CPU
STOP.
Refresh
("Clears
compulsorily "
not checked)
Block data
assurance per
station
Set the block guarantee of cyclic
data per station.
Disable
("Enable
setting" not
checked)