User`s manual
(10/n)
LEN130391
Setting Item Description
Example for
settings
Remarks
No.of boads in
module
Set the "No. of boards in module "
for which the network parameters
are to be
set.
1
Start I/O No
Set the "Start I/O No." for the master
station.
0000
Operational settings
Set the following:
・Parameter name
・Data link err station setting
・Case of CPU Stop setting
・Block data assurance per station
Refer to next
page.
Even if the Parameter
name is not set, this will not affect the
operation of the CC-Link system
Type Set the station type. Master station
Mode
Set the CC-Link mode. Remote net
(Ver.2 mode)
All connect count
Set the total number of connected
stations in the CC-Link system
including reserved stations.
2 (modules)
Remote input
(RX)
Set the remote input (RX) refresh
device.
X1000
Device name - Select from X, M, L, B, D,
W, R or ZR.
Device number - Within the range of the
device points that the CPU has.
Remote output
(RY)
Set the remote output (RY) refresh
device.
Y1000
Device name - Select from Y, M, L, B, T, C,
ST, D, W, R or ZR.
Device number - Within the range of the
device points that the CPU has.
Remote register
(RWr)
Set the remote register (RWr)
refresh device.
W0
Device name - Select from M, L, B, D, W,
R, or ZR.
Device number - Within the range of the
device points that the CPU has.
Remote register
(RWw)
Set the remote register (RWw)
refresh device.
W1000
Device name - Select from M, L, B, T, C,
ST, D, W, R, or ZR.
Device number - Within the range of the
device points that the CPU has.
Special relay
(SB)
Set the link special relay (SB)
refresh device.
SB0
Device name - Select from M, L, B, D, W,
R, SB or ZR.
Device number - Within the range of the
device points that the CPU has.
Special register
(SW)
Set the link special register (SW)
refresh device.
SW0
Device name - Select from M, L, B, D, W,
R, SW or ZR.
Device number - Within the range of the
device points that the CPU has.
Retry count
Set the number of retries for "Retry
count", when a communication error
occurs.
3
Automatic
reconnection station
count
Set the number of modules that can
return to system operation by a
single link scan.
1
Standby master
station No.
Set the station number for the
standby master station
Blank
Blank: No standby master station specified.
PLC down select
Set the data link status for "PLC
down select", when a master station
programmable controller CPU error
occurs.
Stop
Scan mode setting
Set whether the link scan for the
sequence scan is synchronous or
asynchronous.
Asynchronous
Delay information
setting
Set for the link scan delay time.
0
Station information
settings
Set the station data. Refer to the
next page.