User`s manual
5 - 5
MELSEC-
A
5 PROGRAMMING
(2) Initial setting by remote device station initialization procedure
registration
(a) Setting the target station number
Set the station number to which initial setting will be made.
Set the target station number to "1".
(b) Setting the procedure registration
When the initial data processing request flag (RX18) turns on and the
remote device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65SBT-64AD.
Procedure Execution Condition Execution
Initial data processing request flag (RX18) turns on
A/D conversion enable/prohibit specification: channels 1, 2: enable
(RWw0: 0003
H)
Input range setting : channel 1: 0 to 5V
: channel 2: user range setting 1
(RWw1: 51
H)
Moving average processing count setting: channel 2: 16 times
(RWw5: 10
H)
CH.1 moving average processing specifying flag: sampling processing
(RY00: OFF)
CH.2 moving average processing specifying flag: moving average processing
(RY01: ON)
Initial data processing completion flag (RY18) is turned on.
Initial data setting request flag (RY19) is turned on.
Initial data processing request flag (RX18) turns off Initial data processing completion flag (RY18) is turned off.
Initial data setting completion flag (RX19) turns on Initial data setting request flag (RY19) is turned off.
(c) Setting results
The setting results are shown below.