5 PROGRAMMING
5.2 Conditions of Program Example
The program examples in this chapter are created under the following conditions.
(1) System configuration
PLC CPU
Master station
(X0 to X1F/Y0 to Y1F)
I/O (Output 64 points)
(Y60 to Y9F)
AJ65SBT-64AD
(Station number 1)
I/O (Input 64 points)
(X20 to X5F)
(2) Relationships between programmable controller CPU, master
module and AJ65SBT-64AD
Programmable controller
CPU
Device X
Device Y
Device D
X400 to X40F
X410 to X41F
Y400 to Y40F
Y410 to Y41F
D200
D201
D202
D203
Device D*
D300
D301
D302
D303
Master module
Address
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
E0
H
E1
H
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
160H
161H
Remote register (RWw)
RWw0
RWw1
RWw2
RWw3
1E0H
1E1
H
1E2
H
1E3
H
Remote register (RWr)
RWr0
RWr1
RWr2
RWr3
2E0H
2E1
H
2E2H
2E3
H
AJ65SBT-64AD
(Station number 1)
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
Remote register (RWw)
RWw0 A/D conversion
enable/prohibit specification
RWw2 Moving average processing
count setting
RWw3 Reserved
RWw1 Input range setting
Remote register (RWr)
RWr0 CH.1 digital output value
RWr2 CH.3 digital output value
RWr3 CH.4 digital output value
RWr1 CH.2 digital output value
* In the program example (refer to Section 5.5) that uses the RRPA instruction
(automatic refresh parameter setting) with the ACPU/QCPU (A mode), RWr0 to
RWr3 are assigned to D456 to D459.
POINT
Some CPU modules may not accept the devices used in the program example in
this chapter. For the setting ranges of the devices, refer to the user's manual of the
CPU module used.
For an A1SCPU, for example, devices X100 and Y100 or later cannot be used. Use
devices such as B and M.