User`s manual
3 - 10
MELSEC-
A
3 SPECIFICATION
3.5 Remote I/O Signals
This section describes the assignment and functions of the remote I/O signals.
3.5.1 Remote I/O signal list
Remote inputs (RX) mean the input signals from the AJ65SBT-64AD to the master
module, and remote outputs (RY) mean the output signals from the master module to
the AJ65SBT-64AD.
In communications with the master station, the AJ65SBT-64AD uses 32 points of the
remote inputs (RX) and 32 points of the remote outputs (RY). Table 3.4 indicates the
assignment and names of the remote I/O signals.
Table 3.4 Remote I/O Signals List
Signal direction: AJ65SBT-64AD Master Module Signal direction: Master Module AJ65SBT-64AD
Remote input (RX) Signal name Remote output (RY) Signal name
RXn0 CH.1 A/D conversion completion flag RYn0 CH.1 moving average processing specifying flag
RXn1 CH.2 A/D conversion completion flag RYn1 CH.2 moving average processing specifying flag
RXn2 CH.3 A/D conversion completion flag RYn2 CH.3 moving average processing specifying flag
RXn3 CH.4 A/D conversion completion flag RYn3 CH.4 moving average processing specifying flag
RXn4 CH.1 range error flag
RYn4
to
RY(n+1)7
Reserved
RXn5 CH.2 range error flag
RXn6 CH.3 range error flag
RXn7 CH.4 range error flag
RXn8
to
RXnB
Reserved
RXnC
E
2
PROM write error flag
RXnD
Reserved
RXnE
RXnF Test mode flag
RX(n+1)0
to
RX(n+1)7
Reserved
RX(n+1)8 Initial data processing request flag RY(n+1)8 Initial data processing completion flag
RX(n+1)9 Initial data setting completion flag RY(n+1)9 Initial data setting request flag
RX(n+1)A Error status flag RY(n+1)A Error reset request flag
RX(n+1)B Remote READY
RY(n+1)B
to
RY(n+1)F
Reserved
RX(n+1)C
to
RX(n+1)F
Reserved
POINT
The reserved devices given in Table 3.4 are used by the system and cannot be
used by the user.
If the user has used (turned on/off) any of them, we cannot guarantee the functions
of the AJ65SBT-64AD.