Specifications
MELSECNET/MINI-S3
43
A High Speed Remote I/O Networking System
■ Up to 512 remote I/O points
The MELSECNET/MINI-S3 remote I/O networking system
allows a wide variety of remote I/O modules to be con-
trolled by a central station. A maximum of 64 remote
stations can be connected to one network loop, either using
fiber optic and/or twisted pair cables. Up to 512 points of
data can be refreshed between the master and remote
stations in less than 3.2ms.
■ RS232C interface unit
Communications with devices such as bar code readers and
ID controllers is possible when connecting this unit to
MELSECNET/MINI. Other general purpose devices can also
communicate with this unit using a no protocol format.
■ AJ71PT32-S3/AJ71T32-S3 specifications
Part number AJ71PT32-S3 AJ71T32-S3
Cable type Fiber optic or twisted pair Twisted pair
Maximum number of I/O stations 64
Maximum number of I/O points 512
I/O refresh time 3.2 to 18msec (18msec for all stations)
Communication speed 1.5M baud
Maximum distance between stations
50m (164ft) for fiber optic, 100m (328ft) for twisted pair (no limit for overall distance)
Number of I/O points required 32 / 48*
Current consumption (5VDC) 0.35A 0.30A
■ A Series inverters and FX Series PLCs
Both FREQROL A Series inverters and the FX Series PLCs
can be connected to MELSECNET/MINI. Inverters can be
controlled and monitored from the master station and the
FX PLCs can exchange data with the master station.
■
AJ71PT32-S3/AJ71T32-S3
MELSECNET/MINI-S3 master module
The AJ71PT32-S3/AJ71T32-S3 MELSECNET/MINI-S3 master
module allows the host QnA/A Series PLC to control up
to 64 remote I/O stations connected on the MELSECNET/
MINI-S3 networking system. The master module carries out
high speed communication processing with the remote
units connected to the network it controls. More than one
master module can be used per PLC CPU, up to the
maximum I/O points of the host CPU.
AJ71PT32-S3 is compatible with both fiber optic and
twisted pair cable networks.
AJ71T32-S3 is compatible with twisted pair cable networks.
*By setup switch
RyansElectric.com