Specifications

CC-Link
AJ65BT-R2 Remote RS232C Interface
Any RS232C equipped devices such as bar code reader or weighing
meter, etc. can be connected to CC-Link through this RS232C
interface module. Because of the high performance of CC-Link
system, those RS232C devices can be located far away from PLC
while retaining quick data access time.
AJ65BT-G4 Remote Programming Interface
This is a programming interface that may be located anywhere in
the CC-Link system. For adjustment or maintenance activities, a
PLC can be accessed from anywhere in the network for up/down
loading of program, monitoring, and some testing functions with
GPP or MEDOC programming software. Furthermore, access is also
given to other PLCs through CC-Link, QnACPU and
MELSECNET/10.
Specifications: Remote RS232C interface
Model AJ65BT-R2
Number of channels 1 channel
Communication method Full duplex
Synchronization Asynchronous
RS232C interface
Transmission speed 300/600/1200/2400/4800/9600/19200
Data format Start: 1, Data: 7/8, Parity: 0/1, Stop: 1/2
Error detection Parity check: None/Even/Odd
Flow control DTR/DSR (ER/DR) or DC 1/DC 3
Cable distance 15m (49.21ft)
Specifications: Remote programming interface
Model AJ65BT-G4
Interface RS422, channel
Function Program up/down load, Program monitor, Device data up/down load, Device test
Target PLC type MELSEC-A, AnS, QnA, Q2AS
Master/local PLC on the same CC-Link
Accessible PLC location PLC on MELSECNET/10 or MELSECNET
II
through master/local PLC on the same CC-Link
Note: Access through MELSECNET/10 or MELSECNET
II
is available only when the target PLC is QnA/Q2AS.
Remote I/O type Intelligent device
Occupied station numbers 1 (RX/RY: 32 points each, RWr/RWw: 4 points each)
Repeater modules for the CC-Link system
Repeater modules extend the total distance of the CC-link
system and can realize T-break connections in it. The
modules also simplify wiring in places where it is difficult to
set cables.
AJ65SBT-RPS/AJ65SBT-RPG module
Extends the total distance up to 7.8km with a slower com-
munication speed
Realization of T-break connections possible
AJ65SBT-RPT module
Extends the total distance up to 13.2km with a slower
communication speed
Realization of T-break connections possible
AJ65BT-RPI-10A/B module
Realization of infrared ray transmission from 0m to 100m
Capable of monitoring the status of transmissions between
a Master station and remote I/O stations.
Specifications
AJ65SBT-RPS/AJ65SBT-RPG AJ65STB-RPT AJ65BT-RPI-10A/B
Speed 156k/625k/2.5M/5M/10Mbps 156k/625k/2.5Mbps
Maximum row 3 2 10 2
Maximum number of stations 64
Optical communication SI/QSI/GI cables
CC-Link
transmission
Angle of beam spread:
±2
(
transmission distance within 50m
)
±1
(
transmission distance, 50m to 100m
)
42